1.03
This parameter is used to set a temperature, at which compressor starts to slow down its speed.
Also, the set value is based on
Δ
T.
Compressor always works with its maximum allowable speed, if actual water temperature is lower
than
[
]
(
in
heating mode) or higher than [Tset+1.03]
(
in
cooling mode).
When actual temperature is between [Tset-1.03
,
Tset] ιν
heating
mode
or [Tset, Tset+1.03] in cooling
mode, compressor will
adjust its working speed, to balance the total heating output and system load.
This setting is to keep a balance between comfort and energy saving. If this value is set too big even if
the room is not warm (or cool) enough, compressor will slow down its speed quite soon to save energy.
If this value is set too small, even if the room is warm (or cool) enough, compressor will slow down its
speed
quite late, which consumes more power
.
It’s more like a setting that tells the heat pump unit which temperature range you
'
d prefer to have the
heat pump stayed in.
For
example, in heating mode, if Tset
=
48
℃,
and 1.03
=
2
℃,
compressor will work as hard as possible
to get 46
℃
as soon as possible. Then compressor will lower its speed. If even the compressor works in
its lowest
allowable speed, but actual water temperature still goes over [Tset+1.01], unit stops.
Tset-1.03
△
T Compressor Speed-Reduction
1.04
Set an ideal water temperature for cooling via this parameter.
1.05
)
Heating Curve Function
Set whether heating curve function is needed or not.
If heating curve function is not needed, set 1.05
=
OFF
,
and then you can set a fixed water temp.
under heating mode via parameter 1.19
“
Set Temp For Heating
”
1.06~1.15
Set The Heating Curve
1.06
1.07
1.08
1.09
1.10
1.11
1.12
1.13
1.14
1.15
When 1.05
=
ON
,
user
can set a heating curve which fits his house, by adjusting the settings of
parameter 1.06
~
1.05
)
Set Temp. For Cooling
Ambient Temp. 1
Ambient Temp. 2
Ambient Temp. 3
Ambient Temp. 4
Ambient Temp. 5
Water Temp. A/Ambient Temp. 1
Water Temp. B/Ambient Temp. 2
Water Temp. C/Ambient Temp. 3
Water Temp. D/Ambient Temp. 4
Water Temp. E/Ambient Temp. 5
Working In Heating
Compressor ON
Tset-1.03
Compressor Speed Down
Full Speed
Temp. Drops Lower
Than [Tset-1.03]
Stay in [Tset -1.03, Tset +1.01]
Temp. Increases Higher
Than [Tset+1.01]
Compressor Stop
Temp. Drops Lower Than [Tset-1.02]
69
7. Operation Instruction