Parameterlist heatapp! base
S. 107
16.3.3
Room settings
Menu /
Parameter
Adjust-
ment
range
Description
Display condition
depending on the
EG connection
with gateway
Display condition
depending on the
EG connection
without gateway
… Expert / room group resp. room / room settings
T2
B
R
e
la
is
0-
1
0
V
OT
o
ff
T2
B
R
e
la
is
0-
1
0
V
OT
o
ff
Comfort
temperature
Economy
temperatu
re
…21,0…
28.0° C
Setting the room setpoint temperature for heating mode.
X
X
X
X
X
X
X
X
X
X
Economy
temperature
Set-back-
tempera-
ture
…20,0° C…
Comfort
temperatu
re
Adjustment of the reduced room setpoint temperature for
heating mode.
X
X
X
X
X
X
X
X
X
X
set-back
temperature
Anti-freeze
temperatu
re
…
18,0°C
…
economy
temperatu
re
Setting the room setpoint temperature for set-back
operation.
X
X
X
X
X
X
X
X
X
X
anti-freeze
temperature
4,0
…
16,0°C
…
set-back
temperatu
re
Setting the room setpoint temperature for frost protection
operation.
X
X
X
X
X
X
X
X
X
X
start
optimation
off,
0,5 … 8,0 h
Setting of the maximum bringing forward of the switch-on
time (switching time) depending on the outdoor
temperature.
X
X
X
X
boost-offset
0,5
…
2,0
…
5,0 K
Setting of the increase of the room setpoint temperature
with activated boost scene in the heatapp! app.
X
X
X
X
X
X
X
X
X
X
local
operation
on
,
off
Activate the local setpoint setting on heatapp! drive and
heatapp! sense control. The setting applies to all heatapp!
drive and heatapp! sense control registered in this room.
X
X
X
X
X
window
shutdown
off
5 … 240
Min
on
Off: Disables window shutdown, information only.
Min.: Blocking of the heating function (adjustment to frost
protection temperature) for the set duration. Turning
wheel is blocked; scenes only take effect after closing the
window.
On: Blocks the heating function for the duration of the
window opening. Turning wheel is blocked; scenes only
take effect after closing the window.
X
X
X
X
X
Содержание T2B
Страница 21: ...Installation and initial operation S 21 Fig 8 Connection variant wall base MS K Fig 9 Connection variant THETA...
Страница 66: ...Control S 66 10 2 6 3 Network Fig 44 Network configuration gateway...
Страница 121: ...Technische Daten S 121 18 3 Drilling template heatapp base heatapp base T2B Fig 76 Drilling template heatapp base...