Parameterlist heatapp! base
S. 106
16.3.2
Basic settings
Menu /
Parameter
Adjust-
ment
range
Description
Display condition
depending on the
EG connection with
gateway
EG connection
with gateway
Display condition
depending on the
EG connection
without gateway
… Expert / room group resp. room / basic settings
T2
B
R
e
la
is
0-
1
0
V
OT
o
ff
T2
B
R
e
la
is
0-
1
0
V
OT
o
ff
request
Outside
temperatu
re
control*,
room
control
Selection of the request for the room/room group.
*
If there is no outdoor sensor in the system, room control
takes place.
X
X
X
X
screed
off
,
functional
heating,
laying
heating,
functional-
and laying
heating
Selection of the screed heating programme for the room /
room group, if supplied by a heating circuit.
X
X
frost
protection
off, -20
…
3
…
29 °C
(resp.
summer
operation
mode
)
Setting of the outdoor frost protection temperature to
activate the frost protection function for the room/room
group.
X
X
X
X
summer
operation
mode
off, frost
protection
…
20,0
…
30 °C
Setting of the outdoor temperature value to activate
summer operation for the room/room group.
X
X
X
X
room blocking
off
,
0,1 … 5 K
If the room setpoint is exceeded by the limit value set here,
the demand on the energy generator is cancelled.
X
X
X
X
X1
X1
X1
X1
room
thermostat
off
,
0,1 … 5 K
If the room setpoint is exceeded by the limit value set here,
the valves of the zones controlled by heatapp! floor close.
X
X
X
X
X
frost
protection
mode
anti-freeze
temperatu
re
, set-
back
temperatu
re
Selection of the temperature level at which the frost
protection function for the room/room group is to be
regulated when activating the “Vacation” or “Standby”
scenes. Regulation of room frost protection after set frost
protection temperature or regulation of room frost
protection after set settling temperature.
X
X
X
X
X
X
X
X
X
X
name
Alphanum
eric, max.
15
characters,
no special
characters
Enter the name for the room/room group.
X
X
X
X
X
X
X
X
X
X
Note
X1 when using a heatapp! sense wire
Содержание T2B
Страница 21: ...Installation and initial operation S 21 Fig 8 Connection variant wall base MS K Fig 9 Connection variant THETA...
Страница 66: ...Control S 66 10 2 6 3 Network Fig 44 Network configuration gateway...
Страница 121: ...Technische Daten S 121 18 3 Drilling template heatapp base heatapp base T2B Fig 76 Drilling template heatapp base...