7 Commissioning the HDG Euro – Commissioning the HDG Euro
70
HDG Euro V3.0 with HDG Lambda Control 1 - V 1 - en
©
HDG Bavaria GmbH 06/2008
Testing system components
How to proceed
The test of the respective component is started by pressing the
Plus
button.
The test is stopped by pressing the
Minus
button.
The test is conducted on the next component by pressing the
Arrow
button.
The component test is stopped by simultaneously pressing the
Plus
and
Minus
buttons.
1.
Press the
Arrow
button.
✓
The message “
Selection/information
” appears in the
display.
2.
Press the
Plus
button.
✓
The display changes to
Selection/settings
.
3.
Press the
Plus
button again.
✓
The display changes to
Selection/component test
.
4.
Press the
Arrow
button.
✓
The message “
O2 sensor test
” appears in the display.
5.
Press the
Plus
button.
✓
The O2 sensor test will begin.
(Duration = 720 seconds)
✎
See the paragraph “ Calibrating the lambda sensor”, section
“5.2 How to proceed”, chapter “5 Cleaning and maintaining the
HDG Euro”.
✓
The O2 sensor test is completed.
6.
Press the
Arrow
button.
✓
The display advances to the next component:
primary pump
.
Caution!
For safety reasons, the system component test may only be
conducted when there is no fuel in the boiler and there are no
remaining embers.
Please note!
Test can only be conducted in
“Heat production off”
mode.