Section 2:
Installation
Copyright © 2011 Haskris Company
5
www.haskris.com
Version R1600-X-R407C-XXX Instruction Manual Rev00
See space requirements listed in Section 2.3 below to plan the location of
the R1600.
The R1600 requires free vertical discharge space above the chiller. Ensure
no eaves, overhangs, or any other obstructions are present to restrict the air
space above the chiller. Remove any snow and/or ice accumulation on top
of chiller prior to start-up.
The ambient air temperature range for Model R1600 is -20°F to +120°F. A
lack of cool/fresh air to the condenser will result in reduced cooling
capacity and possibly the complete shutdown of the refrigeration
compressors. Avoid dusty areas and periodically check to make sure that
the condenser is clean (refer to
Section 5.3 for air-cooled condenser
cleaning instructions).
Secure the system to the concrete pad or roof curb using the mounting holes
(see Figure 2.1) at the base of the chiller. Consult local codes for proper
anchoring methods.
PLEASE NOTE: Do NOT affix any labels or stickers to the interior or
exterior of the R1600 chiller with Refrigeration Service Contractor’s
name and/or contact information. The only labels permitted on the
interior or exterior of the R1600 come supplied by the factory.
2.3
2.3
2.3
2.3 Space Requirements
Space Requirements
Space Requirements
Space Requirements
R1600 Dimensions
67’’W* x 67’’D* x 75’’ H (170cm W* x 170cm D* x 191 cm H*
*
*
*
* Add 4” (10.2cm) for Mounting Flange
Required Minimum Clearances for Service
Front: 36” (91.5cm)
Left:
36” (91.5cm)
Back: 36” (91.5cm)
Right: 36” (91.5cm)
!!!!