Section 3:
Start-Up
Copyright © 2011 Haskris Company
17
www.haskris.com
Version R1600-X-R407C-XXX Instruction Manual Rev00
3.1
3.1
3.1
3.1 Remov
Remov
Remov
Remove
e
e
e Liquid Refrigerant
Liquid Refrigerant
Liquid Refrigerant
Liquid Refrigerant Prior to Compressor Start Up
Prior to Compressor Start Up
Prior to Compressor Start Up
Prior to Compressor Start Up
Energize the crankcase heaters (#8 in wiring diagram located inside
your Haskris system, inside the top panel of the supply/return side of the
R1600) 12 hours prior to start-up to evaporate any liquid refrigerant
accumulated in the refrigeration compressors during shipment. The
compressors crankcase heaters will energize when main power is
supplied to the R1600 and is not controlled by the three-position switch
located on the R1600 Control Panel (See R1600 Control Panel
description at the beginning of Section 3).
Failure to energize the compressor crankcase heater 12 hours prior to
the no-load start-up will shorten the lifetime of the compressor.
If for some reason the crankcase heater cannot be energized for 12
hours prior to the no-load start-up, the Cooling Mode – Stop - Pump
Only Mode switch (See Section 4) may be toggled between the center
position (Stop) and the left position (Cooling Mode) rapidly 3 or 4 times,
before switching the system ON permanently. Use this method only as a
last resort.
Haskris recommends leaving main power to the R1600 on at all times.
!!!!