Section 5:
Maintenance Recommendations
Copyright © 2011 Haskris Company
34
www.haskris.com
Version R1600-X-R407C-XXX Instruction Manual Rev00
5
5
5
5.3
.3
.3
.3 Air
Air
Air
Air----Cooled Condenser Cleaning
Cooled Condenser Cleaning
Cooled Condenser Cleaning
Cooled Condenser Cleaning
The Haskris R1600 chiller includes two air-cooled condensers which draw a
substantial amount of air across the condenser fins and coil. As dust and debris
collect, heat transfer becomes less efficient, resulting in the loss of cooling
capacity. To remove the accumulation of debris, vacuum the condenser fins
thoroughly during regular services. Additional cleaning may be required in some
extreme environments. Nearby vegetation, such as cotton wood trees, etc. should
be avoided or removed if found to be problematic. A brush may be used to loosen
compacted debris being careful not to damage the fins or the condenser coil
coating. HASKRIS DOES NOT RECOMMEND THE USE OF A PRESSURE
WASHER AS THIS MAY DAMAGE THE FINS OR CONDENSER COIL COATING.
5
5
5
5.4
.4
.4
.4 Finding the Pressure Setting of the Bypass Valve
Finding the Pressure Setting of the Bypass Valve
Finding the Pressure Setting of the Bypass Valve
Finding the Pressure Setting of the Bypass Valve
To find the pressure setting of the bypass valve, restrict the flow water from the
Haskris R1600 chiller by closing the Supply Side Isolation Valve (Figure 2.9).
THIS SHOULD NOT BE DONE WHILE THE EQUIPEMENT ATTACHED TO THE
THIS SHOULD NOT BE DONE WHILE THE EQUIPEMENT ATTACHED TO THE
THIS SHOULD NOT BE DONE WHILE THE EQUIPEMENT ATTACHED TO THE
THIS SHOULD NOT BE DONE WHILE THE EQUIPEMENT ATTACHED TO THE
CHILLER IS IN OPERATION.
CHILLER IS IN OPERATION.
CHILLER IS IN OPERATION.
CHILLER IS IN OPERATION. The pressure gauge will then indicate the valve set-
point. As noted above, the valve does not snap open and shut. It will crack open
approximately 16-18 psi (1.1-1.2 Bar) below its set-point, depending on the valve.
The valve continues to open gradually, increasing the amount of bypass, as
pressure approaches the valve set-point. When the set-point is reached, all of the
flow from the pump is being bypassed. For this reason, the valve should be set a
minimum 20 psi (1.4 Bar) above the normal operating pressure to ensure full flow
of the pump through the closed loop.