power must not be turned off except when unit is being
serviced.
8.
Properly label supply and return lines over the insulation with
either a flow arrow or the words ‘SUPPLY’ and ‘RETURN’.
9.
Properly sleeve and insulate pipe penetrations through all roof
and/or wall penetrations to protect pipe from potential
damage.
10.
Properly sleeve and insulate pipe penetrations through all roof
and/or wall penetrations to protect pipe from potential
damage.
11.
Provide and install a 12’ long loop of 1-1/2” reinforced
opaque hose between supply and return outlets in equipment
room to allow for start-up and no load testing of R1600
chiller. Hose will be used by HMSA for connection of heat
exchanger at time of installation.
12.
Provide and install a ball valve on both the supply and return
lines at the indoor WW4 heat exchanger to allow isolation
for service or unit replacement if necessary. The R1600
chiller includes factory installed isolation valves at both the
supply and return connections.
13.
Provide a temperature gauge (0-100°F) on both the supply
and return side between the ball valve and indoor WW4 heat
exchanger to measure supply and return temperature at the
WW4 heat exchanger.
14.
Provide a pressure gauge (0-100psig) on the supply side
between the ball valve and indoor WW4 heat exchanger to
measure supply pressure at the WW4 heat exchanger.
15.
Provide an in-line flow meter (5-25gpm) on the return side
between the ball valve and indoor WW4 heat exchanger to
measure return flow at the WW4 heat exchanger. Haskris
recommends Blue-White Series F-420N Variable Area Flow
Meter sized to match the piping line size. Provide a
moveable sleeve over the flow meter to prevent exposure to
light when flow meter is not being read. Any prolonged
exposure to light may promote biological growth in the water
lines.