All interconnecting piping should be run per HMSA Standard Details.
2.6.1 Piping Installation
Install all water piping runs and components using the following
guidelines:
1.
Excessive particles in the pumping system can reduce the
efficiency of the system or cause damage to components.
Care should be taken to maintain the internal cleanliness of
the piping. If flux is used during the soldering of any
connection, Haskris recommends removing excess flux from
any external solder joint.
2.
Install Type ‘L’ hard copper piping in a method as short and
direct as possible in order to minimize the pressure drop
across the piping. See Worksheet 1 (located at the end of
this Instruction Manual) to calculate recommended line size.
Consult your state, local, or municipal codes for other
requirements.
3.
Install vibration isolators at the R1600 on both glycol solution
supply and return lines.
4.
Install a drain at the base of every rise to allow for complete
drainage of piping.
5.
Install air vents at all high points in the system to eliminate air
from the system.
6.
Properly support all piping where required. Do NOT attach
any form of piping support directly to R1600 chiller.
7.
Install heat trace on all piping exposed to low ambient
temperatures (34°F [1°C] or below) and cover with a suitable
thickness of closed-cell, UV resistant insulation. Route power
for heat trace from a separately fused disconnect. Identify
disconnect as heat trace power source with a warning that