CLEAR VFD FAULTS
CLEAR VFD FAULTS
CLEAR VFD FAULTS
CLEAR VFD FAULTS
1.
Press the down arrow key until
is flashing on the display panel. No LEDS
should be lit indicating that the VFD is in programming mode.
2.
Press enter and then the down arrow key until the screen reads “o1-01”. Press
enter to change the second value to 4 so the screen now reads “04-01”. Press
enter again and change the last value to 11. The screen should now read “o4-
11”.
3.
Press the enter key again. Press the reset key and now the second zero should be
flashing. Press the up arrow and change the selection to 1. Press enter and the
display will display the word end then return to the screen from figure 1. The fault
history has been erased.
4.
Return to the home screen by pressing the “esc” key until the display shows “F
0.00” again.