The display range can also be zoomed in/out by touching it. To do this, the desired range
must be marked horizontally. The starting point must be indicated by touching the screen
and swiping to the right. The display range is then marked in grey. As soon as the touch
screen is no longer being touched, the marked area will be enlarged to fill the maximum
displayable size in the display window.
The display range will change so that the current values are shown in the right-hand section.
Screenshot
The plotter’s display range is stored locally on the device.
Pressing this button opens a new window for selecting the zones to be displayed in the
plotter.
Back to the zone selection.
5.3.2.4
Control
1.
2.
Operation > Control
The “Control” menu item contains settings that can be used to influence the control behaviour of zones. These are,
firstly, control parameters for the control algorithm and, secondly, the heating signal fed to the heating units.
5.3.2.4.1 Control dynamics
Value
Description
Automatic
optimisation
The automatic control optimisation determines the P, I and D components of the
controller automatically. This is only performed for zones in normal operation directly
after the outputs are switched on and is marked "Optimised" in the status text below
the zone designation. The zones to be automatically optimised when they are switched
on can be determined by activating and deactivating the function. To do this, the zones
should first be selected and the function then activated/deactivated with the
corresponding buttons.
Factory setting: automatic optimisation active
P component P band of the PID controller
The output level is reduced linearly before attaining the setpoint value. Increasing
the P band causes a slower transient response.
Setting limits: 0… 100%
Factory setting: 5%
I component
I component of the PID controller.
The reset time TN of the PID controller is specified in this setting. Increasing the
reset time causes a slower transient response.
Setting limits: 999s
Factory setting: 80s