32 HASCO hot runner
Sensor voltage
The voltage in the sensor line is
inadmissibly high
-
Wiring error
-
Connection to
neighbouring zone
-
Insulation damage
Collective warning
Mains voltage
Fluctuations detected in the mains
voltage.
-
Mains voltage
fluctuations
Collective warning
Residual current
Residual current flowing in the affected
phase.
-
Moisture
-
Insulation damage
Collective warning
or
Sensor fracture
The zone is not connected to the sensor.
-
Sensor connection
-
in the controller
-
in the connecting line
-
in the mould
Collective warning
or
collective alarm
Switch-off temperature
The current temperature is above the
maximum permitted temperature.
-
Setting limit
-
Manual operation
-
Wiring error
Collective alarm
Excessively high temperature
The current temperature is above the limit for
an excessively high temperature.
-
Setting limit
-
Manual operation
-
Wiring error
Collective alarm
Excessively low temperature
The current temperature is below the limit
for an excessively low temperature.
-
Setting limit
-
Manual operation
-
Heating power
-
Wiring error
Collective alarm
No connection to load
No current flows when the outputs are
controlled with an output level > 0%
-
Connection to mould
-
Cable/plug or heating
unit defective
-
Triac defective
-
Triac coupler defective
Collective alarm
Sensor polarity
The sensor polarity has been reversed.
Increasing temperatures are recorded as
negative temperature values.
-
Wiring error
Collective alarm
Defective fuse
No current flows despite the outputs being
controlled
-
External fuse
-
Internal fuse
-
Insulation damage
Collective alarm
Defective triac
Current flows when the outputs are not being
controlled.
-
Triac
Collective alarm
Relay fault
The output relay of the relevant zone is
defective.
-
Internal hardware error
Collective alarm