Chapter 3 - Installation
3-17
Remote Functions
Wiring Diagram
(See Fig. 3-25)
•
Wire Size: (Twisted Pair Shielded)
Maximum - 12 AWG
Minimum - 22 AWG
•
Momentary Functions require 100 mSEC or greater to ground for
proper activation. Use remote functions ground only for activating
remote functions.
•
Use twisted pair shield cable only. Maximum length 60 inches.
CAUTION
REMOTE FUNCTIONS ARE NOT ISOLATED. DO NOT BUNDLE WIRING
FROM REMOTE FUNCTIONS WITH POWER CABLE, RELAY CABLE OR
WITH ANY OTHER HIGH ENERGY CABLES.
Remote Functions
St
a
rt
Pa
u
se
A
bor
t
Rs
tT
o
t
Pr
in
t
A
R
e
fill
Re
m
Gn
d
Input Power Wiring
Diagram (See Fig.
3-26)
WARNING
NOTE:
FIG. 3-25 REMOTE FUNCTIONS WIRING DIAGRAM
DO NOT OPERATE WITH INCORRECT LINE VOLTAGE. TO DO SO WILL
RESULT IN PROPERTY DAMAGE OR PERSONAL INJURY. CHANGING
THE INPUT VOLTAGE RATING BETWEEN 120 AND 240 VAC REQUIRES
MODIFICATIONS TO THE POWER/RELAY CIRCUIT BOARD AND
RELAY OUTPUT BOARD. THIS PROCEDURE SHOULD ONLY BE DONE
BY AUTHORIZED PERSONNEL. FOR FURTHER ASSISTANCE
CONTACT
HARDY PROCESS SOLUTIONS
, CUSTOMER SUPPORT.
Remote functions wires carry very low voltage signals. They operate on TTL ground
levels. The Remote Functions wires should be shielded and routed away from the
relay output wires and all other AC voltage lines to prevent electrical induction and
false ground triggering. Maximum length 60 inches.
•
The HI 2160RC
PLUS
is factory configured to operate from either
120 or 240 VAC, 50 or 60 Hz power. Check the model number of
your unit to verify the voltage. If the unit is configured for 240
VAC, a "B2" will be printed on the name plate.
•
The power and relay circuit card filters conditions AC power. How-
ever, for noisy power lines, external conditioning may be required.
Contact Customer Support for more information.
•
The AC power should be supplied by a "clean" primary line,
directly from the power panel. This line should not supply any other
Содержание HI 2160RC PLUS
Страница 1: ...HI 2160RCPLUS Rate Controller Operation and Installation Manual ...
Страница 23: ...HI 2160RCPLUS MANUAL 2 6 ...
Страница 32: ...Chapter 3 Installation 3 9 FIG 3 12 FRONT PANEL WITH BRACKETS FROM FACTORY FIG 3 13 BEZEL INSTALLATION DIAGRAM ...
Страница 46: ...Chapter 3 Installation 3 23 Interconnect Wiring Diagram See Fig 3 33 FIG 3 33 INTERCONNECT WIRING DIAGRAM ...
Страница 48: ...Chapter 3 Installation 3 25 FIG 3 35 SECURE MEMORY MODULE FIG 3 36 INSTALLING REMOVING SECURE MEMORY MODULE ...
Страница 49: ...HI 2160RCPLUS MANUAL 3 26 ...
Страница 67: ...HI 2160RCPLUS MANUAL 4 18 ...
Страница 91: ...HI 2160RCPLUS MANUAL 5 24 ...
Страница 151: ...HI 2160RCPLUS MANUAL 7 12 ...
Страница 187: ...HI 2160RCPLUS MANUAL 8 36 ...
Страница 197: ...1 2 3 4 5 6 V V I I VOLTAGE CURRENT HI 2160RCPLUS MANUAL 9 10 FIG 9 5 CONNECTOR WIRING DIAGRAM FOR CONTROL OUTPUT CARD ...
Страница 207: ...HI 2160RCPLUS MANUAL 9 20 ...
Страница 219: ...Data Worksheets WKSHT 6 ...