35
5.1 Operation Setup
5 Function Setup
Pressing [MENU] button on the operation screen gets into setup menu where various parameters can
be set.
When [OPERATION SETUP] button is pressed on the function setup screen, the operation setup
screen is displayed.
- Operation Type : Program control or fixed control
- Limit SV change rate : used to prevent rapid SV changes during fixed control operation.
- Limit MV change rate : Setup when concerned about problems caused by rapid changes
in controlled output. When it is set, the output rate is limited to 10 % per
second (5 % per 0.5 sec).
- Fixed operation time : if this time is set, when the time expires during fixed control operation,
the operation stops automatically.
- Power-out Handling : If power goes down and recovers, the type of operation is set.
STOP ->Operation stopped state, COLD-> Control from beginning, HOT-> control from the stopped point
- Buzzer Setup : Touch sound, ON/OFF
- Touch Input Lock : When set, only [MENU] and [NEXT] respond. Prevents mistakes.
- Automatic Screen Power Down : To preserve lifespan of LCD and BACK LIGHT, when there are no
inputs for certain period of time, the screen powers down
automatically. {Does not affect the operation}
- Purging : Suppresses over shoot. {Time taken to reach the intended value delays}