42
ON/OFF switching, and therefore a suitable value must be set.
(If PID GAIN P-BAND value is 0, it operates in ON/OFF control mode).
- Heated Side Output Direction : Setup basic output direction. The heating side is by
default, opposite direction, the cooling side is by default, right
direction. If heat control is done by cooler etc, it could be necessary
to change the output direction.
- Heated Side Output Range : Setup the limit for minimum output, maximum range.
(The control output is automatically scaled to this range)
- Cooling side output direction : Opposite to the heated side output.
- Cooling side output range : Setup the limit for minimum output, maximum range.
(The control output is automatically scaled to this range)
- Transmission Output Type : Setup transmission type for each channel. (PV, SV, H.MV, C.M.V)
- Temperature Output Range for Transmission Output : When outputting 4 - 20 mA of power,
setup corresponding temperature range.
- Sensor Disconnection Output Setting : Setup transmission output value when sensor is
disconnected. {Select 0 mA or 4 mA}.
- Fix Power Output : When the product is shipped, the power output of 4 - 20 mA is set
with precision, however, in case of imprecision during simultaneous use with
other instruments, the power output can adjusted within the range of ±5 %.
Time signal is used when certain signal generation is desired in relation to time during program mode
operation. In contrast, inner signal is used when output signal accordance with the PV and SV values
during operation, is desired. Mostly, in constant temperature and humidity, it is used mainly to control
cooler, according to the range setting.
- Target I/S Setup : Select I/S signal originator.
- I/S type setup : Select I/S signal source.
- I/S operation range : Select range for signal generation
- I/S range direction : Select inclusive range and exclusive range.
- I/S Delay Time : Set I/S signal generation delay. If PV2 is the source, irresponsiveness
value at I/S signal OFF. (Prevents frequent ON/OFF in coolers etc).
6.3 Inner Signal Setup