HAMWORTHY HEATING LTD
WARMWELL
500001091/F
Figure 2.2 Performance and General Data Information
GENERAL DATA
60
95
140
Boiler Input High Fire - kW (Gross)
63.4
101.0
150.0
Boiler Input High Fire - kW (Nett)
57.1
90.9
135.0
Boiler Input Low Fire - kW (Gross)
39.0
38.6
46.6
Boiler Input Low Fire - kW (Nett)
35.1
34.8
42.0
Boiler Output High Fire (Condensing) - kW
59.0
93.0
135.0
Boiler Output High Fire (Non-Condensing - kW
54.0
86.0
128.0
Boiler Output Low Fire (Condensing) - kW
36.3
35.5
41.9
Boiler Output Low Fire (Non-Condensing) - kW
33.2
32.9
39.8
FLUE DATA
Nominal Flue Diameter. - mm
150
Approx. Flue Gas Temperature (Condensing) - °C
45
45
45
Approx. Flue Gas Temperature (Non-Condensing) - °C
65
65
65
Approx. Flue Gas Volume @ 9.0% CO
2
- m
3
/h*
82.8
132.0
197.2
GAS DATA
Gas Inlet Connection
R¾
R1
Nominal Gas Inlet Pressure - mbar
20
Maximum Gas Inlet Pressure - mbar
25
Gas Manifold Pressure High Fire - mbar
12.5
9.5
11.0
Gas Manifold Pressure Low Fire - mbar
5.0
1.5
1.2
Gas Flow Rate High Fire - m
3
/h
5.92
9.44
14.10
Injector Marking / Dia. - mm
3.1
4.2
4.4
No. Burner Bars / Injectors
5
WATER DATA
Water Connections
Flow - Rc2 Return - Rc2
Maximum Water Pressure - bar g
6
Water Content - litres
36
43
57
Minimum Water Flow Rate @ 15°C
∆
T Rise - litre/s
0.94
1.46
2.15
Waterside Pressure Loss @ 15°C
∆
T Rise - mbar
35.0
86.0
206.0
Design Water Flow Rate @ 20°C
∆
T Rise - litre/s
0.70
1.10
1.61
Waterside Pressure Loss @ 20°C
∆
T Rise - mbar
17.6
50.0
117.7
Minimum Water Flow Rate @ 22°C
∆
T Rise - litre/s
0.64
1.00
1.46
Waterside Pressure Loss @ 22°C
∆
T Rise - mbar
15.0
41.0
97.0
ELECTRICAL DATA
Normal Supply Voltage
230V ~ 50Hz
Power Consumption (maximum) - W
190
Shunt Pump Output (optional)
230V ~ 50Hz fused @ 2A
4
Pressure Switch Setting (Normal) High Fire - mbar
1.8
2.4
2.4
Pressure Switch Setting (Normal) Low Fire - mbar
1.5
1.5
0.4
120
132
119
55
50
120
117
50
45
45
65
173.5
11.6
2.0
3.0
0.4
12.6
4.1
50
1.91
158.0
1.43
91
1.30
75
4
5
80
86.5
78
33.3
30
78
72.5
31.2
27.0
45
65
111.0
10.7
1.9
0.9
0.4
7.9
3.75
4
43
1.21
63.0
0.91
32.0
0.83
24.0
* NOTE!
Flue gas volumes are based on a gross flue gas temperature of 15°C at 1013.25mbar
4
Содержание Warmwell 120