HAMWORTHY HEATING LTD
WARMWELL
500001091/F
Appendix A Warmwell Automatic Ignition
INFORMATION RELATING TO PROPANE FIRING
NOTE:-
LPG FUELS - IT IS STRONGLY RECOMMENDED THAT, ON LPG INSTALLATIONS, GAS DETECTION
EQUIPMENT IS FITTED. THIS EQUIPMENT SHOULD BE POSITIONED NEAR THE BOILER AND AT LOW
LEVEL. IT IS ALSO IMPORTANT THAT THE SPACE HOUSING THE BOILER IS ADEQUATELY
VENTILATED AT HIGH AND LOW LEVEL. REFER TO MAIN INSTALLER’S GUIDE.
1.0 INTRODUCTION
The operation of the Warmwell range of boilers on
LPG-Propane (3
rd
family)
I
3P
is similar to that on
Natural Gas (2
nd
family)
I
2H
and the design and
installation details described in the main body of the
installer’s guide should be followed. There are
however, differences in the construction and setting
of the propane fired boiler which are as follows: -
a) The main gas injectors (located in the gas
manifold) are replaced with those detailed the
Performance and General Data Information table
below.
b) The nominal gas inlet pressure for propane
should be 37mbar.
c) Relevant labels are replaced to indicate the
appropriate gas for which the boiler is set up to fire.
The following tables and paragraphs, using the
same numbering system as the main installer’s
guide, highlight the different values and procedures
to be used when firing propane, and should be used
in conjunction with the Main Installer’s Guide.
Figure 2.2 Performance and General Data Information
* NOTE!
Flue gas volumes are based on a gross flue gas temperature of 15°C at 1013.25mbar
GENERAL DATA
60
95
120
Boiler Input High Fire - kW (Gross)
63.4
101.0
N/A
Boiler Input High Fire - kW (Nett)
58.4
93.0
N/A
Boiler Input Low Fire - kW (Gross)
30.3
42.3
N/A
Boiler Input Low Fire - kW (Nett)
27.8
39.0
N/A
Boiler Output High Fire (Condensing) - kW
59.0
93.0
N/A
Boiler Output High Fire (Non-Condensing) - kW
54.0
86.0
N/A
Boiler Output Low Fire (Condensing) - kW
28.1
38.9
N/A
Boiler Output Low Fire (Non-Condensing) - kW
25.8
36.0
N/A
FLUE DATA
Approx. Flue Gas Temperature (Condensing) - °C
45
50
N/A
Approx. Flue Gas Temperature (Non-Condensing) - °C
60
70
N/A
Approx. Flue Gas Volume @ 9.0% CO
2
- m
3
/h*
85
125
N/A
CO
2
- %
8.5
9.5
N/A
GAS DATA
Nominal Gas Inlet Pressure - mbar
37
Maximum Gas Inlet Pressure - mbar
Gas Manifold Pressure High Fire - mbar
15.0
17.0
N/A
Gas Manifold Pressure Low Fire - mbar
4.0
3.0
N/A
Gas Flow Rate High Fire - m
3
/h
- kg/h
2.4
4.6
3.8
7.2
N/A
Injector Marking / Dia. - mm
2.3
2.9
N/A
45
Pressure Switch Setting (Normal) High Fire - mbar
1.8
2.4
N/A
Pressure Switch Setting (Normal) Low Fire - mbar
1.5
1.5
N/A
140
150.0
138.1
49.8
45.8
135.0
128.0
44.8
42.4
50
70
201
8.5
24.0
2.5
3.0
0.6
5.7
10.7
2.9
41