HAMWORTHY HEATING LTD
WARMWELL
500001091/F
For example: - 2 Purewell 120kW Boilers being fed by 65mm NB pipe with 6 elbows between gas meter and
boiler header can have a maximum length of 72m - (6 x 2m) = 60 metres run to achieve a 1mbar loss.
Note! Information above is based on IM/16.
The above table expresses pipe lengths from gas meter to appliance which will produce approx. 1mbar pressure
loss. This table must be used in conjunction with losses of various fittings fitted in the gas line shown below.
Figure 5.3 Gas Flow in Pipes
Total Gas Input
m³/hr
NB
20mm
25mm
40mm
50mm
65mm
80mm
100mm
4.73
10
42
-
-
-
-
-
5.92
-
25
180
820
-
-
-
7.10
-
16
120
540
-
-
-
8.27
-
11
85
380
-
-
-
9.44
-
-
62
280
900
-
-
11.19
-
-
42
185
580
-
-
12.36
-
-
33
145
470
-
-
14.1
-
-
25
110
345
-
-
18.88
-
-
12
56
180
-
-
22.38
-
-
-
38
120
750
-
24.72
-
-
-
30
96
600
-
28.20
-
-
-
22
72
440
-
33.57
-
-
-
15
47
290
-
37.08
-
-
-
11
37
235
-
42.30
-
-
-
-
27
170
810
44.76
-
-
-
-
24
150
730
49.44
-
-
-
-
19
115
570
56.40
-
-
-
-
14
86
430
61.80
-
-
-
-
11
71
340
70.50
-
-
-
-
-
51
245
74.16
-
-
-
-
-
46
220
84.60
-
-
-
-
-
34
165
Maximum length of gas pipe (Metres)
Fitting Type(NB)
20mm
25mm
40mm
50mm
65mm
80mm
100mm
Per elbow
0.5m
0.5m
1.0m
1.5m
2.0m
2.5m
3.5m
Per Tee
0.5m
0.5m
1.0m
1.5m
2.0m
2.5m
3.5m
Per 90°Bend
0.3m
0.3m
0.3m
0.5m
0.5m
1.0m
1.5m
8