HAMWORTHY HEATING LTD
51
UPTON FLOOR STANDING SERIES
500001340/C
•
Enduser will be displayed on the screen use rotary knob to select Engineer press
OK,
Time and date will be
displayed on the screen.
•
Use rotary knob to select Boiler.
•
Use rotary knob to select line number 2322 pump speed min, press
OK
100% will flash adjust as required
then press
OK
.
•
Use rotary knob to select line number 2323 pump speed max, press
OK
100% will flash adjust as required
to match min speed then press
OK
.
•
When finished press ESC twice to return to main screen on HMI.
•
On the HMI press
OK,
time and date will appear.
•
Press and hold the
I
button for 3
-
5 seconds
•
Enduser will be displayed on the screen use rotary knob to select Engineer press
OK,
Time and date will be
displayed on the screen.
•
Use rotary knob to select Diagnostics heat generation press
OK.
•
Use rotary knob to select line number 8310, Boiler flow temp will be displayed on the screen.
•
Use rotary knob to select line number 8314, Boiler return temp will be displayed on the screen.
Optional extras required for this configuration:
Hamworthy Flow and return manifold kit
Legend
E = End user
I = Commissioning
F = Heating engineer
Menu
Operating Line
User Level
Function
Setting
Configuration
5890
F
Relay output QX1
Boiler pump Q1
Optional extras required for this configuration:
None
Boiler Parameter Settings: Individual Boiler Shunt Pumps (Relay Output QX1)
External time clock with weather compensation
Legend
E = End user
I = Commissioning
F = Heating engineer
Menu
Operating Line
User Level
Function
Setting
LPB System
6600
F
Device address
1
6630
F
Cascade Master
Automatically
Heating Circuit 1
900
F
Operating mode Changeover
Automatic
Configuration
5710
F
Heating circuit 1
On
5977
F
Function of input H5
HCS
5978
F
Contact type H5
NC
Heating Circuit 1
740
F
Flow temp min set point
50
741
F
Flow temp max set point
80
720
F
Heating curve slope
3
726
F
Heating curve slope adaption
On
Operation section
26
F
Operation lock
On
Hot water mode
No display
Note:
Use H5 wiring connection to enable boiler requires volt free enable from time clock.
Optional extras required for this configuration:
External air sensor
– QAC34
Part number 533901457
Room sensor choice
– QAA55—Offset adjustable room sensor
Part number 533901589
– QAA75—Programmable room sensor
Part number 533901587
Boiler Parameter Settings: Single Boiler