HAMWORTHY HEATING LTD
52
UPTON FLOOR STANDING SERIES
500001340/C
Legend
E = End user
I = Commissioning
F = Heating engineer
Menu
Operating Line
User Level
Function
Setting
Configuration
5892
F
Relay output QX3
Boiler pump Q1
Note:
The QX3 terminals have live outputs on NO & NC connection together with neutral & earth this will facilitate pow-
ering the valve open and closed.
Optional extras required for this configuration:
None
Boiler Parameter Settings: Individual Boiler Flow Isolation Using Motorised Valve
Internal time clock with two heating circuits, DHW & boiler shunt pump
Legend
E = End user
I = Commissioning
F = Heating engineer
Menu
Operating Line
User Level
Function
Setting
Configuration
5890
F
Relay output QX1
Boiler pump Q1
5931
F
Sensor input BX2
Common flow
Sensor B10
5977
F
Function input H5
None
5710
F
Heating Circuit 1
On
5715
F
Heating Circuit 2
On
6021
F
Function extension Module 2
Heating Circuit 1
6022
F
Function extension Module 3
Heating Circuit 2
6054
F
Function input H2 Module 2
Room Stat HC1
6062
F
Function input H2 Module 3
Room Stat HC2
Domestic Hot Water
1610
F
Nominal Set Point
60°C
Domestic Hot Water
-
additional parameters may need to change
Extension module AGU 2.550A109 are require for each addition heating circuit to be controlled. Maximum of
three additional extension modules can be accommodated per boiler.
Heating mode
Auto symbol
Hot water mode
On
Note:
For this application, the Function extension modules 2 & 3, with respect to their parameter setting as heating cir-
cuits 1 & 2, have pre
-
defined outputs for each extension module as shown in the table below.
Wiring connections on heating circuit extension module AGU 2.550A109
QX21
QX22
QX23
BX21
BX22
H2
Multifunctional
*
*
*
*
*
*
Heating circuit 1
Y1
Y2
Q2
B1
*
*
Heating circuit 2
Y5
Y6
Q6
B12
*
*
Heating circuit 3
Y11
Y12
Q20
B14
*
*
Boiler Parameter Settings: Single Boiler
Note:
To check operation of pumps, mixing valves & thermostats select: engineer – diagnostic consumers – parameters
8730 to 8779
Optional extras required for this configuration:
2x Heating circuit extension modules AGU2.55A109
Part number 563605669