HAMWORTHY HEATING LTD
53
UPTON FLOOR STANDING SERIES
500001340/C
Heating sensor kit
– QA236
Part number 563605673
2x Room sensor choice
– QAA55—Offset adjustable room sensor
Part number 533901589
– QAA75—Programmable room sensor
Part number 533901587
DHW sensor kit
– QA236
Part number 563605674
Connections on heating circuit extension module AGU2.550A109:
QX21—Switched live—Mixing valve opening
QX22—Switched live—Mixing valve closing
QX23—Switched live—Heating circuit pump
(Contactor required for pump)
BX21—Flow temperature sensor—Heating circuit
H2—Heating circuit room thermostat—Basic type no/nc switch vfc (Only use if optional room sensor QAA55 or
QAA75 are not specified)
Boiler Parameter Settings: Multiple Boilers
Sequence control using integral Master and Slave configuration
Single primary pump set for fixed flow rate operation (pump will have to
be low energy type)
The table below shows all available settings up to the heating engineer level. However, certain operating lines
may be hidden, for security purpose
Legend
E = End user
I = Commissioning
F = Heating engineer
Menu
Operating Line
User Level
Function
Setting
LPB System
6600
F
Device address
Boiler 1 set to 1 (master)
Boiler 2 set to 2
Additional boilers set to 3, 4 ect.
6601
F
Segment address
Boilers all set to 0
6640
F
Clock mode
Boilers 1 set to
Master
Boilers additional set to
Slave with remote setting
6630
F
Cascade
Boiler 1 set to always
Boilers additional set to
Autonomously
Configuration
5710
F
Heating Circuit 1
Boiler 1 set to on
Boilers additional set to off
5890
F
Relay output QX1
Boiler 1 set to
Cascade pump Q25
5931
F
Sensor input BX2
Boiler 1 Master
Common flow sensor B10
Boilers additional set to none
6117
F
Central compensation set up
Boilers all set to 5
6200
F
Save sensors
Boilers all set to yes
Internal time clock settings
Settings must be programmed to master boiler
Menu
Operating Line
User Level
Function
Setting
Time program
500
E
Mon
-
sun: Mon
-
Fri:
As req
Heating
501
E
1st period on
Circuit 1
502
E
1st period off
503
E
2nd period on
504
E
2nd period off
505
E
3rd period on
506
E
3rd period off
Configuration
5710
F
Heating circuit 1
On
External enable—e.g. Remote time clock
Settings must be programmed to master boiler