MAN1544-5
32
5.3.7
Agent
If Yes was selected in the SYSTEM menu the Sub
–
Menu seen below will be available. Press
Enter
to access
the sub-menu. The sub-menu consists off;
Release
Press Sw
Auto Delay
Man Delay
No LCP’s
LCS Buzzer
Solenoid
Pyrogen
Metron
NO/NC/None
N/O & Mech
0
–
60s
0
–
60s
0 - 16
Normal /
Silent
Using
Move Right or
Move Left select either
Release,
Sense
Switch,
Auto Delay, Manual Delay
or
the
Number of Local Control Panels ( LCP’s )
, and / or
Inhibit LCS Buzzer
then the
key to access the
menu and the
Move Up or
Move Down keys to set the required function or number.
In the
Delay
Menus the
Move Up and
Move Down keys are used to set or alter the time
delay in 5 second increments.
Press
to update each Program and
Cancel
to back out of the Menu.
Release
Identifies the type of release mechanism. [ Constant / Solenoid / Pyrogen / Metron ].
RELEASE
SOLENOID
RELEASE
PYROGEN
RELEASE
METRON
RELEASE
CONSTANT
Press Sw
PRESS SW
N / O
PRESS SW
N / C
PRESS SW
NONE
PRESS SW
N / O & MECH
Sets the type of monitor release contact. [ NO / NC / None N/O & Mech
–
manual release ]
Auto Delay
AUTO DLY
15
Sets the delay for the automatic release of the agent
. [ 0
–
60 seconds set in 5 second increments ]
Man Delay
MAN. DLY
35
Sets the delay for when the agent is released manually.
[ 0
–
60 seconds set in 5 second increments]
No LCS’s
LCS
1
Tells the FACP how many Local Control Panels are in service.
[ 0
–
4 ]