Controls & Indicators
–
Front Panel
2.1
System Controls & Indicators
The front panel controls for the ZoneSense PLUS - AR consists of twelve push buttons and an optional
Normal / Enabled key switch.
Figure 1: AS4428 8 Zone Front Panel Controls and Indicators
2.2
Level of Access
Access to the FACP is restricted to three levels of authorisation.
AS4428 requires panel controls to be behind a 003 keyed door.
Level 1: (No Password Required)
By pressing the Menu button access to Level 1 is gained to the read only FAULT, STATUS display and
Password entry menu.
Level 2 (If set Pre-commissioning Password is factory set at 2222)
To gain access to the Level 2 TEST and ISOLATE MENUS a fixed 4 digit Level 2 Password or a key to the
control ENABLE switch is required.
Level3: (Pre-commissioning Password factory set at 3333)
Level 3 SYSTEM and PROGRAM menus can only be accessed by a set Level 3 password that can not be
deleted.
Panels fitted with a key switch have access to level 2 with the switch enabled and then 3 via the password.
Without the key switch access to level 2 is by opening the door and then to level 3 via the password.
Note:
If the keypad controls are not used for a period of 2 minutes the display will return to the default
screen.