background image

 

MAN1544-5 

 

 

 

 

45

 

6.12

 

Manual Mechanical Release of the Agent 

With agent release systems, a manual mechanical means can be provided to release the agent. 

If the pressure switch is activated (indicating that the agent has been released),and the agent release add-
on has not activated the selected activation circuit, then the following will occur: 

 

Stage 1 output is switched to +24VDC and stage 1 relay is closed 

 

Stage 2 output is switched to +24VDC and stage 2 relay output is closed 

 

Light the agent release LED on the ARC and LCSs 

 

The FACP activates its Bell, ASE, Warning System, Plant, and Alarm outputs 

 

Activate gas-fired relay output 

6.13

 

Monitoring of the Pressure Switch 

Due to the requirements of 5.9 Manual Mechanical Release of the Agent, the pressure switch input conveys 
two pieces of information: 

 

When the pressure switch input is active, it signals that the agent has been released. The release 
can be as a result of the agent release add-on or due to a manual mechanical release.  

 

When the pressure switch is not active, it signals that there is a full bottle of agent available to be 
discharged.  

In order for the agent release module to respond to a manual mechanical release, the pressure switch must 
have been previously not active, to signify that a full bottle of agent is available 

Содержание Ampac ZoneSense Plus

Страница 1: ...Fire detection and evacuation solutions that save lives ZoneSense Plus Operation Programming MAN1544 5...

Страница 2: ...displayed on the LCD Z7 ZONE SEVEN 2 To Isolate External Bell press 3 To Isolate Warning System press 4 To Acknowledge Alarm press ALARM LED will go steady 5 To Isolate Alarm press ISOLATED LED will b...

Страница 3: ...ss STATUS press FAULTS Press TEST press ISOLATES Press ZONES ISOL D press ZONE 1 ACTIVE Moving to ZONE 2 press ZONE 2 ACTIVE press OR to ISOLATE Zone 2 accessed and ISOLATED To DE ISOLATE press the IS...

Страница 4: ...3 3 1 1 Outputs 14 3 1 2 Brigade 14 3 1 3 Relays 15 3 1 4 Fire Fan 15 3 1 5 Agent 15 3 1 6 Sounders 15 3 1 7 Inputs 16 3 1 8 Voltage 16 3 1 9 Software 16 3 2 FAULTS 17 4 Level 2 Access 18 4 1 Tests 18...

Страница 5: ...ease Operation 39 6 5 Manual Mode 39 6 6 Auto Mode 40 6 6 1 Single Zone Activation 40 6 6 2 Dual Zone Activation 41 6 6 3 Manual Activation 43 6 7 Service Switch 43 6 8 Lock Off Valve 43 6 9 Fault Sup...

Страница 6: ...jor world standards To ensure these standards are not compromised in any way installation staff and operators should Be qualified and trained for the task they undertake Be familiar with the contents...

Страница 7: ...TATUS display and Password entry menu Level 2 If set Pre commissioning Password is factory set at 2222 To gain access to the Level 2 TEST and ISOLATE MENUS a fixed 4 digit Level 2 Password or a key to...

Страница 8: ...d Zone Alarm LED will flash and the Buzzer will sound By pressing Acknowledge the LED s become steady the Buzzer will be silenced and a zone s can be Isolated or Reset Alarm Red Alarm is a general fir...

Страница 9: ...ove right through a menu or the options to be set Move Up takes the cursor up through the menus and or options Move Down takes the cursor down through the menus and or options Cancel is used to return...

Страница 10: ...vailable to the FACP Power Fault Yellow Common fault to either the mains or DC system power supply System Fault Yellow Indicates a failure of the FACP to provide mandatory functions software failure E...

Страница 11: ...rm fault isolate information and prompts for system commands come programming Alarm Fault and Isolate information is accessed through the Main Menu When the FACP is in its normal state a default scree...

Страница 12: ...Menu consists of Level 1 Level 2 Activate Control Level 3 Enter Password STATUS FAULTS TEST DISABLES SYSTEM PROGRAM Press the Move Right Move Left key to move through the menu Press to access the sub...

Страница 13: ...n the FACP FAULTS Note Use Cancel at any time to step back out of the current Menu 3 1 STATUS Status allows the operator to select and view the current state operating conditions of the active compone...

Страница 14: ...OFF NORMAL WARN SYS OFF NORMAL ALARM OFF FLT Figure 2 Sample Output Screens Meaning The O P is either On activated and Normal or Off de activated and Normal or On activated and Isolated or Off de acti...

Страница 15: ...ontrol status 1 to 4 FAN 1 ON Figure 5 Sample Fire Fan Screen 3 1 5 Agent Press then Move Left or Move Right to select the Agent OR press Move right to access Sounders The LCD indicates the Agent Rele...

Страница 16: ...d the Battery Voltage will be displayed pressing Move Right will display the Charger Voltage approx 27 2volts pressing Move Right again will display the System Voltage BATT V 27 2V CHRGR V 27 2V SYSTE...

Страница 17: ...information Accessing information on 2 Faults FAULTS 2 flts Press F 1 2 ZONE 7 Press Right keys to scroll F 2 2 ZONE 8 Or FAULTS 2 flts Press F 1 2 ZONE 7 Press to view detail ZONE 7 OPEN CCT LCD Scr...

Страница 18: ...menu Press then select the Zone by using the Move Up and or Move Down keys until the desired Zone number is displayed press to start the test 4 1 1 Alarm Test Once the test is commenced the Buzzer wi...

Страница 19: ...Alarm Outputs will operate the corresponding Zone Alarm LED will flash and the buzzer will sound The Zone will stay in Alarm until the MCP or detector under test is reset or the test is aborted by pre...

Страница 20: ...the Battery Test will commence that is the Charger will be disconnected from the battery and a dummy load placed across the battery for 60 seconds The battery voltage should be above that specified 23...

Страница 21: ...2 1 Main Control Board Zone Relay Board or Sounder Board Isolates Press Enter and use the Move Left or Move Right keys to select the Zone Relay or Sounder number then the Move up to key isolate or Mo...

Страница 22: ...Bell is Isolated the External Bell LED will be illuminated Warning System is Isolated the Warning System LED will be illuminated ACF is Isolated the ACF Fault Isolate LED will be illuminated ASE Alar...

Страница 23: ...ove to the next number to be set This operation has to be repeated four times as the PASSWORD is a four digit code If a number is incorrect it can be changed by using the Move Left and Right keys to p...

Страница 24: ...been fitted and will not appear in the Programming Menu ERTH NO BRIGADE YES RLY CARD YES Figure 12 Typical Screen examples of the System Menu Buzzer Earth Mon Brigade Relay Board Fire Fan Agent Resoun...

Страница 25: ...nt to the desired number 0 to 8 maximum of 8 5 2 3 Code Code is the National Standard the Panel complies with This is factory set and can not be altered CODE AS4428 Back out to the Main Menu using the...

Страница 26: ...s are used to select the Zone number and the Move Up and ZONE 2 NORMAL ZONE 4 AVF ZONE 6 AGENT 1 Figure 13 Sample Zone Screens Move Down keys are used to set the functions within that Zone The functio...

Страница 27: ...nter the zone numbers Press to update the program Note Press Cancel to return to the Zones Menu and then Move Right to access the Clock menu 5 3 2 Clock To set the day and time press and the day will...

Страница 28: ...l set the Zone to activate the output and the Move Down key will set the selected Zone so it does not activate the output WARN SYS 12345678 WARN SYS 12 78 All 8 Zones Selected Zones 1 2 7 and 8 Select...

Страница 29: ...Right and or Move Left keys to select the Zones and the Move Up or Move Down keys to set it to be active or in active Active meaning the Zone Alarm Fault Isolate Input or Switch will operate the Relay...

Страница 30: ...ited Use the Move Up or Move Down keys to set it to active or in active Active meaning the Zone will operate the control where as in active will prevent that Zone from having control ALARM 2 INHIBIT 3...

Страница 31: ...non latching on alarm LATCHING YES LATCHING NO Press to update the Program and to back out of the Menu ACF Isolate Press and the cursor will flash over YES or NO and then the Move Up or Move Down keys...

Страница 32: ...Delay Menus the Move Up and Move Down keys are used to set or alter the time delay in 5 second increments Press to update each Program and Cancel to back out of the Menu Release Identifies the type of...

Страница 33: ...LCD will display Style 1 STYLE 1 Use the Move Up and the Move Down keys to scroll through the different styles Windows for Slip in Label Windows for Slip in Label Windows for Slip in Label Windows fo...

Страница 34: ...e cursor through the structure of the word and the Move Up and Move Down keys to move through the alphabet Z LABELS ZONE 1 Z1 LOBBY Press to update each Program and to back out of the Menu 5 3 12 End...

Страница 35: ...dition can also be confirmed through the Status Menu To remove the key it is necessary for the switch to be in the OFF position Pressing Select toggles the selection of either the Main or Reserve rele...

Страница 36: ...10K EOL This input is used to determine if air conditioning dampers and doors are closed but can be defaulted to the ON condition by terminating the input with a 2K2 EOL Double action switching is ach...

Страница 37: ...as been released For Pyrogen feedback is from the thermal switch If there is no pressure switch fitted the indicator shall be illuminated immediately the agent release signal is activated Selected via...

Страница 38: ...e ON position by terminating the input TB2 7 8 into a 2K2 resistor INITIAL AGENT Yellow Illuminated when the Initial Agent is selected RESERVE AGENT Yellow Illuminated when the Reserve Agent is select...

Страница 39: ...ease sequence is aborted and the sequence is reset This means the stage 1 and stage 2 outputs are switched OFF The FACP treats the isolate of disable condition according to the applicable fire code AS...

Страница 40: ...system inoperative output shall turn on If the lock off valve or the service inhibit is operated after the agent has been released then there is no effect on the stage 1 and stage 2 outputs and the s...

Страница 41: ...he lock off valve or service inhibit switch is operated after the agent has been released then there is no effect on the stage 1 and stage 2 outputs and the selected activation circuit The system inop...

Страница 42: ...ched OFF and the selected activation circuit is switched OFF The system inoperative output is activated and the trigger zone isolated indictor is illuminated If the lock off valve or service inhibit s...

Страница 43: ...vation LED instigate 5 second delay resume at step 6 8 9 No effect 6 7 Service Switch This optional input is used to bring a fault into the system from an external source Requirements for the input ar...

Страница 44: ...he FACP then the trigger zone isolated indicator at the ARC and LCSs is illuminated and the system inoperative output is operated In addition the brigade isolate relay is operated Regarding interfacin...

Страница 45: ...its Bell ASE Warning System Plant and Alarm outputs Activate gas fired relay output 6 13 Monitoring of the Pressure Switch Due to the requirements of 5 9 Manual Mechanical Release of the Agent the pre...

Страница 46: ...s allow for mounting The IP65 ABS enclosure has 10 screws tightened evenly but not over tightened hold the facia in place Do not over tighten 4 holes in the backpan allow for mounting Specifications O...

Страница 47: ...JP 5 1 2 JUMPER NUMBERING 1 2 Disable EXT Mute Disable External Mute for both Internal Buzzer and External Sounder SYNC I O 3 WIRE TONE 2 TONE 1 COM MUTE SINGLE LEVEL DUAL LEVEL ENABLE SOUNDER NOT USE...

Страница 48: ...TIPLE SIGNS ARE USED MAXIMUM OF 6 FIT 10K EOL TO LAST SIGN ON CHAIN 10K NOT REQUIRED FOR SINGLE LEVEL OPERATION SYNC I O 3 WIRE TONE 2 TONE 1 COM TP10 TP1 GND INPUT OUTPUT LEVEL1 LEVEL2 10K TB4 3 4 2...

Страница 49: ...2 OFF NORM SNDR 3 OFF NORM SNDR 4 OFF NORM SNDR 5 OFF NORM SNDR 6 OFF NORM SNDR 7 OFF NORM SNDR 8 OFF NORM INPUT 1 OFF ON INPUT 2 OFF ON INPUT 3 OFF ON INPUT 4 OFF ON INPUT 5 OFF ON INPUT 6 OFF ON INP...

Страница 50: ...U PRESS TO VIEW DETAILS OF EACH FAULT CANCEL PRESS CANCEL AT ANY TIME TO BACK OUT OF THE MENU OR STOP TEST MENU ENTER MENU ENTER CANCEL MENU ENTER F 2 2 FIRE CTRL MENU ENTER MENU ENTER EXAMPLE OF 2 FA...

Страница 51: ...TEST SNDR 4 TEST SNDR 5 TEST SNDR 6 TEST SNDR 7 TEST SNDR 8 TEST MENU ENTER Isolate ISOLATE ZONES 0 ISOL D ZONE 1 ACTIVE OUTPUTS 0 ISOL D RELAYS 0 ISOL D SOUNDERS 0 ISOL D ZONE 2 ACTIVE ZONE 3 ACTIVE...

Страница 52: ...CK OUT OF THE MENU MENU ENTER MENU ENTER MENU ENTER CANCEL MENU ENTER PRESS THESE KEYS TO SET YES NO YES MENU ENTER UPDATE PROGRAM FACTORY SET CAN NOT BE CHANGED EXAMPLE SET RESOUND TO YES THEN MOVE T...

Страница 53: ...ALPHABET NUMBERS TO MOVE THROUGH THE WORD MENU ENTER EDIT TEXT PRESS SW NONE MENU ENTER SET ZONE 12345678 MENU ENTER MENU ENTER EDIT TEXT SELECT FAN 1 2 3 4 MENU ENTER LATCH SELECT RELAY 1 TO 8 MENU...

Страница 54: ...ault LED illuminated Ensure correct panel configuration Check all connections for loose wiring Warning System Fault LED illuminated Check correct E O L is fitted Check wiring is connected correctly RS...

Страница 55: ...Sense PLUS AR is designed and manufactured by AMPAC TECHNOLOGIES PTY LTD 7 Ledgar Rd Balcatta WA 6021 Western Australia PH 61 8 9201 6100 FAX 61 8 9201 6101 Manufactured to Certificate of Compliance N...

Страница 56: ...ILDING EARTH EOL END OF LINE FDS FIRE DETECTION SYSTEM FACP FIRE ALARM CONTROL PANEL FLT FAULT GND GROUND 0 VOLTS NOT EARTH I O INPUT OUTPUT LCD LIQUID CRYSTAL DISPLAY MAF MASTER ALARM FACILITY MCP MA...

Страница 57: ...t for driving ancillary equipment Approved and approval approved by or the approval of the Regulatory Authority concerned Card detect link a link on a module connector to indicate the disconnection of...

Страница 58: ...the common signal alarm and or fault for transmission to the fire control station Bells and other ancillary functions may be initiated from this facility Power Supply that portion of the FACP which s...

Страница 59: ...MAN1544 5 59 UNCONTROLLED DOCUMENT NOTE Due to AMPAC s commitment to continuous improvement specifications may change without notice...

Отзывы: