MAN1544-5
15
3.1.3
Relays
Press Enter then
Move Left or
Move Right to select the required Relay (1
–
8). The LCD read out
for each relay on the Relay Board will indicate if the selected relay is On, Off or Isolated OR Press
Move right to access Fire Fan.
RELAY 8
ON
RELAY 3
OFF
RELAY 6
ISO
Figure 4: Sample Relay Screens
Meaning: A Relay is either On ( activated ), or Off ( deactivated ) or Isolated.
Note:
The relay’s control function is identified in the configuration documentation
3.1.4
Fire Fan
Press
then
Move Right or
Move Left to select view Fire Fan control status 1 to 4.
FAN 1
ON
Figure 5: Sample Fire Fan Screen
3.1.5
Agent
Press
then
Move Left or
Move Right to select the Agent OR press
Move right to access
Sounders. The LCD indicates the Agent Release Board status / release progress.
AGENT
NORMAL
AGENT
ISOLATED
AGENT
STG 1 FB
Figure 6: Sample Agent Normal, Isolated Release in Stage 1 Screens
3.1.6
Sounders
Press Enter then
Move Left or
Move Right to select the required Sounder (1
–
8). OR Press
Move right to access Voltage. The LCD indicates if the selected Sounder Board output is;
SOUNDER 2
ON / NOR
SOUNDER 8
OFF / NOR
SOUNDER 7
OFF / FLT
Figure 7: Sample Sounders Screens
Meaning: Off and Normal, or Off and in Fault, or On and Normal, or On and in Fault, or Isolated and Normal,
or Isolated and in Fault.