MAN1544-5
30
5.3.6
Fire Fan
FAN 2
The sub menu consists of;
Alarm
Inhibit
Function
Latch
ACF Isolate
For:
Alarm
Inhibit
Press
then use the
Move Right and / or
Move Left keys to select the Fire Fan that will be
controlled by the selected functions in the sub - menu .
Press
to access the sub
–
menu then
Move Right and /or
Move Left keys to toggle through
the sub - menu structure. Press
then
Move Right and /or
Move Left keys to select the
Zone/s
that will activate or deactivate the control when it is in alarm or inhibited. Use the
Move Up
or
Move Down keys to set it to active or in-active. Active meaning the Zone will operate the control
where as in
–
active will prevent that Zone from having control.
ALARM
2..................
INHIBIT
3................
For:
Function
Press
and the cursor will flash over the number 0,1 or 2,
then press the
Move Up or
Move Down keys to select the required Function. Selection relies on how the inputs / outputs have been
physically wired from the Fan Termination Board as outlined below.
0:
equates to a 3 wire Start / Stop, Run & Common.
1:
equates to a 4 wire Start / Stop, Run, Stop & Common.
2:
equates to a 5 wire Start / Stop, Run, Stop, Fault & Common.
FUNCTION 2
Press
to update the Program and then
to back out of the Menu.
For:
Latch
ACF Isolate