5.3.1.2 U-pipe system
Figure 43:
U-pipe system for single hole monitoring
Threshold values
Min. distance between the device and the T-piece
4 m
Max. distance between the device and the T-piece
20 m
Max. branch lengths
With low fan voltage 6.5
… 6.9 V
With high fan voltage 9 … 12 V
40 m
50 m
Max. total pipe length per pipe system
With low fan voltage 6.5 … 6.9 V
With high fan voltage 9
… 12 V
100 m
120 m
Min. distance between two aspiration apertures (d)
4 m
Max. distance between two aspiration apertures (d)
12 m
Max. number of aspiration apertures per pipe system
14 units