MAN3184 - TITANUS PRO
•
SENS®
74
Diameter of aspiration apertures
Trigger thresholds
- not possible
O not feasible
Example
If blockage of 4 aspiration apertures of a total of 12 aspiration apertures is
intended to be detected, the airflow monitoring setting switch is to be set to
level II.
Number of aspiration apertures
4
8
12
Item
Punching diameter of the aspiration reducing film sheet [mm]
A
4.0
3.0
2.5
B
-
3.4
3.0
C
-
-
3.0
Number of aspiration
apertures
4
8
12
1 blocked
aspiration
aperture…
I
-
-
2 blocked aspiration
aperture…
II
I
-
3 blocked aspiration
aperture…
O
II
I
4 blocked aspiration
aperture…
O
III
II
5 blocked aspiration
aperture…
O
O
III
6 blocked aspiration
aperture…
O
O
III
… identified when setting level x.
For project planning in compliance with AS ISO 7240-20, level I or II airflow
monitoring must be set.
NOTICE