6.4.1.7 Collective fault contact function
Figure 67:
Jumper settings of the collective fault contact
The contact type (N/C or N/O contact) of the collective fault is set with
jumpers JU2 and JU3. The contact type of the 1st fault contact is adjusted
with jumper JU2 while the 2nd fault contact is adjusted with jumper JU3. The
following table indicates the position of the jumpers.
Contact type
Jumper JU2
Jumper JU3
Pin pair 1+2
Pin pair 2+3
Pin pair 1+2
Pin pair 2+3
N/C contact
(standard)
X
O
X
O
N/O contact
O
X
O
X
Table 8:
Collective fault contact
X = pin pair jumped
O = pin pair open