![Halma Ampac TITANUS PRO-SENS Скачать руководство пользователя страница 95](http://html1.mh-extra.com/html/halma/ampac-titanus-pro-sens/ampac-titanus-pro-sens_technical-manual_4433096095.webp)
MAN3184 - TITANUS PRO
•
SENS®
95
Drill hole intervals
The distances of the aspiration apertures to each other and to the wall of the
duct are listed in the following table.
Duct cross-section
≤ 0.5 m²
Duct cross-section
> 0.5 m²
Distance of aspiration apertures from the wall
100 to 200 mm
200 to 300 mm
Mutual distance between aspiration apertures
100 mm
150 mm
Aspiration aperture
diameter
The diameters of the aspiration apertures are obtained from the number of
aspiration apertures. The precise value can be found in the chapter "Project
planning"
➔
"Simplified pipe project planning".
The pipe connection is achieved with an end cap without drilling.
Arrangement
The aspiration apertures must be arranged against the airflow.
Note for the project planning that the air conditioning ducts for the installation
of the pipe system are often only accessible from two sides.
Example
The following illustration shows two project planning examples of pipe
systems in air conditioning ducts.
Figure 63:
Ducts with small and large duct cross-section
Содержание Ampac TITANUS PRO-SENS
Страница 51: ...MAN3184 TITANUS PRO SENS 51 Figure 34 Pipe shapes...
Страница 61: ...MAN3184 TITANUS PRO SENS 61 Figure 36 Example pipe project planning with pipe accessories...
Страница 118: ...MAN3184 TITANUS PRO SENS 118 Figure 73 Drill hole intervals for bracket type MT 1 mm...
Страница 135: ...MAN3184 TITANUS PRO SENS 135 Figure 84 Attaching the aspiration reducing film sheet...