![Halma Ampac TITANUS PRO-SENS Скачать руководство пользователя страница 112](http://html1.mh-extra.com/html/halma/ampac-titanus-pro-sens/ampac-titanus-pro-sens_technical-manual_4433096112.webp)
MAN3184 - TITANUS PRO
•
SENS®
112
6.4.1.10 Setting the fan voltage of TITANUS PRO·SENS®-SL
Figure 69:
Switching the fan voltage and fan connection terminal strip on the FC-2 or
FC-3 fan control circuit board
The standard setting for the fan voltage is 6.9 V. The fan voltage can be
adjusted according to project planning by plugging or removing the BR1 and/
or BR2 bridges. The symbols used mean:
X = pin pair jumped
O = pin pair open
Fan voltage setting with FC-2
[V]
Bridge BR1
Pin. no 1+2
Bridge BR2
Pin. no 1+2
6.5
O
X
6.9 (standard)
X
O
9
O
O
Fan voltage setting with FC-3
[V]
Bridge BR1
Pin. no 1+2
Bridge BR2
Pin. no 1+2
10
O
X
11 (standard)
X
O
12
O
O
Jumper JU1 on the basic board must always be unplugged.