MAN3184 - TITANUS PRO
•
SENS®
140
7.5.2 Detection in the bypass
Refer to the chapter "Installing the pipe system"
➔
"Air return" for information
on connecting the air return.
Figure 88:
Positioning the air return using the air conditioning duct (bypass) as an
example
To plan aspirating smoke detectors in these areas, see chapter "Project
planning"
➔
"Project planning for forced airflow".
In case of detection in airflows ≥ 2 m/s, additionally return the exhaust air
from the TITANUS PRO·SENS® back into the airflow area. Cut off the end
of the air return pipe at an angle of 45°.
NOTICE
Содержание Ampac TITANUS PRO-SENS