Item
Components
Description
1
Smoke level indicator 1 to 10
1)
(10 yellow LEDs)
Current smoke level
2)
Operation (green LED)
Operating indicator
Main alarm (red LED)
100% smoke level
Pre-alarm 1) (red LED)
66% smoke level
Fault (yellow LED)
Detection unit fault
Infrared interface
Commissioning and fault diagnostics
2, 4
Aspiration pipe connection
For Ø 25 mm pipe system
3
Cable gland
6x M25
5
Cable gland
8x M20
6
Cable entries (small)
2x M20 for cable with Ø of 8 to 12 mm
7
Cable entries (large)
1x M25 for cable with Ø of 9 to 14 mm
(extendable to Ø 14 to 18 mm)
1)
optional
2)
As a result of signal fluctuation with regard to the smoke level in the
transmission range between two display LEDs, the top active LED can
flicker.
3.2.4 Diagnostics
Figure 13:
Diagnostic software for reading the device state.
For maintenance and service, the diagnostic software offers the option to
display the stored and current device state as well as fault messages of the
TITANUS PRO·SENS® on the PC or laptop. Data is transmitted via the
diagnostic interface, which is connected to the X2 plug connector (DIAG) on
the basic board of the TITANUS PRO·SENS® via an adapter cable.
Содержание Ampac TITANUS PRO-SENS
Страница 51: ...MAN3184 TITANUS PRO SENS 51 Figure 34 Pipe shapes...
Страница 61: ...MAN3184 TITANUS PRO SENS 61 Figure 36 Example pipe project planning with pipe accessories...
Страница 118: ...MAN3184 TITANUS PRO SENS 118 Figure 73 Drill hole intervals for bracket type MT 1 mm...
Страница 135: ...MAN3184 TITANUS PRO SENS 135 Figure 84 Attaching the aspiration reducing film sheet...