152
③
BM3 introduction
BM3_1
BM3_2
BM3_3
Outdoor type selection
BM3_1
BM3_2
BM3_3
Outdoor
The outdoor unit
is effective
0
1
1
MRV5-RC outdoor unit
BM3_5
BM3_6
BM3_7
BM3_8
Outdoor horse power
setting
BM3_5
BM3_6
BM3_7
BM3_8
Outdoor horse
OFF
OFF
OFF
ON
8HP
OFF
OFF
ON
OFF
10HP
OFF
OFF
ON
ON
12HP
OFF
ON
OFF
OFF
14HP
OFF
ON
OFF
ON
16HP
OFF
ON
ON
OFF
18HP
OFF
ON
ON
ON
20HP
ON
OFF
OFF
OFF
22HP
②
BM2 introduction
BM2_1
BM2_2
Reserved
OFF
Reserved
BM2_3
Outdoor unit heat mode
setting (valid when BM1_4
=0)
OFF
Normal(default)
ON
Heating only
BM2_4
Outdoor locks the indoor
wireless module MAC
address
(Wireless communication)
Power on,
no action
Locked the indoor wireless module MAC address (default)
Power on,
OFF→ON
Allow all new indoor wireless modules to join (Single-system
power-on search mode during debugging)
BM2_5
Clear the master wireless
module EEPROM
completely
(Wireless communication)
Power on,
no action
Normal(default)
OFF→ON
→OFF
During the debugging process, multiple systems are
powered on at the same time, which causes the m
aster
wireless module
data error, need to do this operation: first
setting the digital tube to 1-1-1, then change the dip swith
from OFF→ON can clear the m
aster wireless module
EEPROM data.
BM2_6
Billing module selection
(Wireless communication)
OFF
No Billing module
ON
Billing module
BM2_7 Quick start selection in high
temperature areas
OFF
Forbid quick start (default)
Group class
(physical master unit is
valid)
ON
Allow quick start
BM2_8
Reserved
OFF
Reserved
Содержание MRV 5-RC AB052MAERA
Страница 1: ...MRV 5 RC Service Manual SYJS 03 2019REV A Edition 2019 03 ...
Страница 3: ......
Страница 55: ...52 AV08 10 12 14IMVURA 4 Center of gravity x X 347 9587 y 471 5454 z 725 6683 y z ...
Страница 56: ...53 AV16 18 20 22IMVURA x X 650 5962 y 380 7255 z 706 5342 y z ...
Страница 106: ...103 2 Dimension 4 19 200 60 25 25 25 249 108 232 84 69 388 73 82 65 103 177 4 44 4 35 277 ...
Страница 116: ...113 2 Preparation before installation ...
Страница 130: ...127 2 Dimension 290 67 410 220 567 137 160 189 57 144 109 159 159 212 393 4 22 65 65 65 65 65 44 65 76 4 52 67 156 830 ...
Страница 162: ...159 One by one valve box PCB code 0151800186A 2 Valve box PCB photo and dip switch setting ...
Страница 165: ...162 One by four valve box PCB code 0151800466 ...