149
(3) Two-core nonpolar communication line with shield shall be adopted for communication lines between the valve
box and the indoor/outdoor unit. Three-core polar communication line with distinguished polarities and shield
shall be adopted for the wire controller connected to the indoor unit.
(4) All valve boxes within one system may share one overcurrent breaker for power supply. But it’s necessary to
compute total current capacity specification.
(5) For wring harness connected to the power terminal block, the terminal shall be pressed with a round (refer to
the following figure).
1) The power terminal block shall not be crimped with 2 wires of different diameters. Otherwise, poor crimp
connection and looseness may lead to abnormal heating or sparking of the line.
2) Refer to the following figure for crimping wires with the same diameter.
1) The maximum wiring length between the outdoor machine and the valve cage, the valve cage and the
indoor machine, and between valve cages is 1000 m at most. The total wiring length is 2000m at most. The
maximum branch number is 16.
2) The maximum wiring length between the valve cage and the wire controller for switching working modes is
500 m at most.
Wire
Insulating sleeve
Round. Press the terminal
(6) Tighten terminal screws with proper screw driver. Screw driver of small dimension will damage the screw head
and fail to tighten properly.
(7) If terminal screws are tightened excessively, they may be damaged. Refer to the following table for tightening
torques of terminal screws:
(8) Power line is forbidden to the communication terminal block because it will damage the circuit control board.
(9) Wiring of communication lines shall be within the following scope. Exceeding the limit will possibly lead to
abnormal communication.
Connect wires with the
same diameter on both
sides
It’s forbidden to connect
two wires on one side
Wires with different
diameters are not allowed
Dimension of terminal screw
Tightening torque (N.m)
M3.5 (terminal block for communication line)
0.80~0.96
M4 (terminal block for power line)
1.18~1.44
M4 (terminal block for ground wire)
1.52~1.86
Содержание MRV 5-RC AB052MAERA
Страница 1: ...MRV 5 RC Service Manual SYJS 03 2019REV A Edition 2019 03 ...
Страница 3: ......
Страница 55: ...52 AV08 10 12 14IMVURA 4 Center of gravity x X 347 9587 y 471 5454 z 725 6683 y z ...
Страница 56: ...53 AV16 18 20 22IMVURA x X 650 5962 y 380 7255 z 706 5342 y z ...
Страница 106: ...103 2 Dimension 4 19 200 60 25 25 25 249 108 232 84 69 388 73 82 65 103 177 4 44 4 35 277 ...
Страница 116: ...113 2 Preparation before installation ...
Страница 130: ...127 2 Dimension 290 67 410 220 567 137 160 189 57 144 109 159 159 212 393 4 22 65 65 65 65 65 44 65 76 4 52 67 156 830 ...
Страница 162: ...159 One by one valve box PCB code 0151800186A 2 Valve box PCB photo and dip switch setting ...
Страница 165: ...162 One by four valve box PCB code 0151800466 ...