156
SW1
SW2 SW3
function
Digital tube LD1 ~ 4 display
Outdoor
unit
address
0-3
7
0
Outdoor unit LEVa1 open degree 0---470pluse
Press START (SW5) for 2 seconds, 1111, enter the
set state: flashing, press UP (SW4) valve fully open,
according to DOWN (SW7) 2min after the valve is fully
closed; automatically exit the setting state
Press STOP (SW6) for 2 seconds, display 0000, quit
the set state, stop flashing display
8
0
Outdoor unit LEVa2 open degree
9
0
Outdoor unit LEVb open degree
10
(
A
)
0
Outdoor unit LEVc open degree
11
(
B
)
0
Outdoor unit output
electromagnetic valve
LD1
:
4WV
:
1 open 0 close――High to the left
LD2
:
SV1
:
1 open 0 close
LD3
:
SV3
:
1 open 0 close
LD4
:
Reserved
,
Display “-”
12
(
C
)
0
Outdoor unit output
electromagnetic valve
LD1
:
SV6
:
1 open 0 close――High to the left
LD2
:
SV9
:
1 open 0 close
LD3
:
SV10
:
1 open 0 close
LD4
:
SV11
:
1 open 0 close
13
(
D
)
0
Outdoor unit output
electromagnetic valve
LD1
:
SVX
:
1 open 0 close
LD2
:
SVY
:
1 open 0 close
LD3
:
Reserved
,
Display “-”
LD4
:
Reserved
,
Display “-”
14
(
E
)
0
Heating belt output
LD1
:
CH1
:
1 open 0 close
LD2
:
CH2
:
1 open 0 close
LD3
:
CHa
:
1 open 0 close
LD4
:
Reserved
,
Display “-”
15
(
F
)
0
Program version
1 representation Ver1.0
SW1
SW2
SW3
function
Digital tube LD1 ~ 4 display
Outdoor
unit
address
0-3
0
1
Pd
Unit: kg, 2 decimal places
2
1
Ps
3
1
Td1
Unit: degree
4
1
Td2
5
1
Tdef
7
1
Toil1
8
1
Toil2
9
1
Toci1
14
(
E
)
1
Tsacc
15
(
F
)
1
Th
SW1
SW2
SW3
function
Digital tube LD1 ~ 4 display
Outdoor
unit
address
0-3
0
15
(
F
)
Reserved
1
15
(
F
)
Tao
25 Unit: degree
2
15
(
F
)
Pd_temp
4
15
(
F
)
Ps_temp
5
15
(
F
)
Tliqsc
6
15
(
F
)
Tsco
8
15
(
F
)
Frequency conversion press INV1 running time
Unit: Min
9
15
(
F
)
Frequency conversion press INV2 running time
Unit: Min
10
(
A
)
15
(
F
)
Frequency conversion press INV1 current CT
Unit: A, 1 decimal places
11
(
B
)
15
(
F
)
Frequency conversion press INV2 current CT
Unit: A, 1 decimal places
12
(
C
)
15
(
F
)
Frequency conversion compressor INV1 DC voltage
Unit: V
13
(
D
)
15
(
F
)
Frequency conversion compressor INV2 DC voltage
Unit: V
Содержание MRV 5-RC AB052MAERA
Страница 1: ...MRV 5 RC Service Manual SYJS 03 2019REV A Edition 2019 03 ...
Страница 3: ......
Страница 55: ...52 AV08 10 12 14IMVURA 4 Center of gravity x X 347 9587 y 471 5454 z 725 6683 y z ...
Страница 56: ...53 AV16 18 20 22IMVURA x X 650 5962 y 380 7255 z 706 5342 y z ...
Страница 106: ...103 2 Dimension 4 19 200 60 25 25 25 249 108 232 84 69 388 73 82 65 103 177 4 44 4 35 277 ...
Страница 116: ...113 2 Preparation before installation ...
Страница 130: ...127 2 Dimension 290 67 410 220 567 137 160 189 57 144 109 159 159 212 393 4 22 65 65 65 65 65 44 65 76 4 52 67 156 830 ...
Страница 162: ...159 One by one valve box PCB code 0151800186A 2 Valve box PCB photo and dip switch setting ...
Страница 165: ...162 One by four valve box PCB code 0151800466 ...