Habasit Italiana S.p.A.
Vittorio Veneto 31029 (TV)
Tel.: ++39(0)438.9113
Fax. ++39(0)438.200545
Regulating Unit PMR-07
Author:
A.T. / KM
CONTROL UNIT
Edition: 04/2006
Page
E-7
Replaces: 10/2005
E.3
PARAMETRIZATION OF THE CONTROL UNIT
Some of the parameters determining the behavior of the control unit can be set by the user. The
sequence for this is as follows:
With the control unit in standby mode, press (and keep pressed) the [PROG] key for 5 seconds.
-> The display shows:
PAS
Press the [PROG] key again
-> The display shows:
0
With the [UP] and [DOWN] arrow keys select the value
55
Press [PROG] again.
-> The display shows the ID of the first parameter:
SPr
(Set point for stop cooling). See table
below about parameter IDs and their meanings.
Press [PROG] again to see the value of this parameter:
-> current value of this parameter is displayed:
50
(This is the default, you may see something
different). See table below as to how to interpret these values.
Change the value with the [UP] and [DOWN] arrow keys.
Scroll down through the list with the [PROG] key. The sequence of display is:
Parameter ID
Parameter value
Next parameter ID
Parameter value
...
Each time a value is displayed you can set it using the [UP] and [DOWN] arrow keys.
To exit the setting mode:
1. Using the [PROG] key scroll all the way down through the parameter list, or
2. Do nothing for 30 s: the control unit falls back to standby mode automatically.
Regulating Unit PMR-07