Habasit Italiana S.p.A.
Vittorio Veneto 31029 (TV)
Tel.: ++39(0)438.9113
Regulating Unit PMR-06
Fax. ++39(0)438.200545
Author:
S.D.T. / KM
SCREEN PAGES MENU
Editon: 12/2005
Page
E-37
Replaces: 05/2005
TABLE
9
-
S
ECURITY TIMES
SECURITY TIMES
T_CC 10.00
from
01.00
to
19.59
min. sec [1 s]
0
Time for thermocouple short circuit alarm:
if the system fails to reach the SPR
cooling set point temperature within this
time the system goes into alarm mode.
DTV
03:00
from
0
to
300
sec [1 s]
0
Minimum time within which a 10°C
temperature change can occur. If the
10°C is exceeded in a shorter time the
system is out of control and triggers an
alarm.
TOV
03:00
from
01.00
to
19.59
min. sec [1 s]
0
Maximum time for plate temperatures
outside the tolerance window TOL. Alarm
triggered if this time exceeded.
TOV2
03:00
from
01.00
to
19.59
min. sec [1 s]
0
Maximum time to reach pressure Set-
Point SET-SP1 (within tolerance window
dP3)
dtC
05:00
from
00:00
to
59:59
min. sec [1 s]
0
Maximum time within which a change of
+10 °C can take place in plate
temperatures. If this does not happen an
alarm is triggered.
TRM
10:00
from
01.00
to
479.59
min. sec [1 s]
0
Maximum time to reach cooling set-Point,
SPR
TABLE
10
-
O
PERATION TIMES
OPERATION TIMES
T_ON 5
from
0
to
5
0.5 sec
0
Minimum time joining plate resistors relay
ON
T_OFF 5
from
0
to
5
0.5 sec
0
Minimum time joining plate resistors relay
OFF.
T_AIR
01:00
from
0.00
to
03.00
min. sec [1 s]
0
Time for Air blow drying
TRF 10.00
from
01.00
to
19.59
min. sec [1 s]
0
Forced cooling time for thermocouple
short circuit alarm