117
7.
Remove the standard storage controller. For more information, see "
8.
Remove the flash card on the storage controller, if any. Remove the screws that secure the
flash card, and then remove the flash card.
Figure 147 Removing the flash card on a standard storage controller
9.
Remove the supercapacitor. For more information, see "
Replacing the power fail safeguard
module for the Mezzanine storage controller
."
10.
Install a new power fail safeguard module. For more information, see "
storage controller and a power fail safeguard module
11.
Install the removed fan cage. For more information, see "
."
12.
Install the removed air baffles. For more information, see "
13.
Install the access panel. For more information, see "
14.
Rack-mount the server. For more information, see "
15.
Connect the power cord. For more information, see "
16.
Power on the server. For more information, see "
Verifying the replacement
Log in to HDM to verify that the flash card and the supercapacitor are in a correct state. For more
information, see HDM online help.
Replacing a GPU module
WARNING!
To avoid bodily injury from hot surfaces, allow the server and its internal modules to cool before
touching them.
Replacing a GPU module without a power cord or with a
standard chassis air baffle
1.
Power off the server. For more information, see "
2.
Remove the server from the rack. For more information, see "
Removing the server from a rack
."
3.
Remove the access panel. For more information, see "
."