GST5000 Intelligent Fire Alarm Control Panel                

               

Installation and Operation Manual (Generic Part) 

 

                             

The Intelligent Solution

 

 

Page 52 

Chapter 7  Commissioning Functions 

The commission mode is set for system commissioning, including registering devices, 
loop card disablement and detector searching functions. 

NOTE: Under commission mode, all the registering information will not be saved. 

When the FACP is restarted, the missing or damaged devices will not be reported. 

These functions are only for commissioning. 

 

7.1  Getting into Commission Mode 

Enter system setup menu (Fig. 6-7), select “3.Working state setup” (Fig.7-1): 

 

 

 

 

 

 

 

 

 

Fig. 7-1 

Press "

" and "

", select 2 "Commissioning State", confirm to enter commissioning 

state, the word "Installer" will appear on top of the screen.  The screen shows as in Fig. 
7-2. 

 

 

 

 

 

 

 

 

 

Fig. 7-2 

Ver  V4.05f

 

Working state setup 

1.

 

Monitoring State 

Installer Ver 1.5

System running

Содержание GST5000

Страница 1: ......

Страница 2: ...ication and Manual Intervention Panel ZCP 8 3 2 1 Structure 9 3 2 2 Functions 9 3 3 Configuration 10 3 3 1 Typical Configuration 10 3 3 2 Optional Configuration 14 3 4 Field Devices 15 3 4 1 A Series of Intelligent Fire Detectors 15 3 4 2 Modules 15 3 4 3 Loop Isolator 15 3 4 4 Manual Call Point 15 3 4 5 Addressable Sounder Strobe 16 3 4 6 GST852RP Repeater Panel 16 3 5 C E Equation and Device Def...

Страница 3: ...e Alarm Screen 31 5 2 2 Disposal of Fire Alarm Signal 34 5 3 Fault Information 34 5 3 1 Screen of Fault Information 34 5 3 2 Disposal of Fault Information 35 5 4 Disable and Enable 35 5 4 1 Use of Disable Enable 35 5 4 2 Disable Enable Devices 35 5 4 3 Browsing Disabled Information 37 5 5 Manual Start and Stop of Loop Devices 38 5 5 1 START STOP Operation through Keypad 38 5 5 2 Operation of the D...

Страница 4: ...50 6 4 5 Zone Browse 50 6 4 6 C E Equation Browse 50 6 4 7 Browsing supervisory data of addressable devices 51 Chapter 7 Commissioning Functions 52 7 1 Getting into Commission Mode 52 7 2 Exiting Commission Mode 53 7 3 Registration at Any Time 53 7 4 Loop Card Disablement 53 7 5 Detector Searching 53 7 6 Protection of C E Equations 53 Chapter 8 Troubleshooting and Regular Checks 54 8 1 General Fau...

Страница 5: ...rm Control Panel Installation and Operation Manual includes two parties generic part and Fireman s Control Panel part This is the generic part Please refer to relative part for description on Fireman s Control Panel Please assign a specific person to keep this manual for occasional use during operation of the GST5000 Intelligent Fire Alarm Control Panel ...

Страница 6: ... smoke detector I 9102 complying with EN 54 7 rate of rise and fixed temperature heat detector I 9103 complying with EN 54 5 intelligent manual call point I 9202 complying with EN 54 11 intelligent reflective beam detector I 9105R complying with EN 54 12 input and output module I 9300 I 9301 complying with GEI 1 084 and loop isolator C 9503 complying with GEI 1 052 3 Graphic display can show 320 2...

Страница 7: ...al installation codes 2 3 Communication Loop Parameters 2 3 1 RS485 Communication Loop NETWORK A B Communication cable for connecting with up to 32 network control panels of different model REPEATER A B Communication cable for connecting with up to 64 repeater panels Recommended Wiring GST FireCable 2E 1 0 2core and Earth 1mm2 CSA subject to local installation codes 2 3 2 RS232 Communication Loop ...

Страница 8: ...arth 1mm2 CSA 1 FIRE ALARM OUTPUT Output Voltage 21VDC 27VDC Output Current 0 5A Terminal Resistor 4 7KΩ 2 F P E OUTPUT Output Voltage 21VDC 27VDC Output Current 0 5A Terminal Resistor 4 7KΩ 3 SOUNDER CIRCUIT OUTPUT Output Voltage 21VDC 27VDC Output Current 0 5A Terminal Resistor 4 7KΩ 4 FAULT OUTPUT NC COM NO Contact Capacity 24VDC 1 0A In fault state NC and COM open NO and COM close 2 6 Dimensio...

Страница 9: ...Part The Intelligent Solution Page 4 CLOCK GST5000 Intelligent Fire Alarm Control Panel Display and operation area LCD Printer Zone indication and manual interventional panel Fireman s control panel 170mm 500mm 700mm Fig 2 1 2 6 2 Rack type GST5000 FACP Dimension L W H 580mm 520mm 1715mm ...

Страница 10: ...ST64ZCP Zone Indication and Manual Intervention Panel GST014FCP Fireman s Switch Panel TEST SELF MANUAL 0 1 GST64ZCP Zone Indication and Manual Intervention Panel GST014FCP Fireman s Control Panel Display and operation area GST64ZCP Zone Indication and Manual Intervention Panel Optional units Optional units Fig 2 2 2 6 3 Console type GST5000 control panel Dimension L W H single unit 555mm 933mm wi...

Страница 11: ...anel TEST SELF 1 0 MANUAL Display and operation area LCD Printer GST014FCP Fireman s Control Panel Optional Units 534mm 370mm 100mm 563mm 750mm 484mm 484mm 1045mm 50mm 1350mm GST64ZCP Zone Indication and Manual Intervention Panel PSU24 6RM Intelligent PSU Fig 2 3 Note There are three types of GST5000 FACP wall mounted type rack type and console type In the following parts of this manual difference...

Страница 12: ...y to turn it off COMMON FAULT Yellow Lit when any fault occurs DISABLED Yellow Lit when connected devices F P E output or SOUNDER output are disabled MUTE Yellow When the FACP sounds alarm pressing MUTE key this LED illuminates and the speaker stops alarming If MUTE key is pressed again or there are new alarms it goes out and the FACP sounds again POWER HEALTHY Green It illuminates when mains or s...

Страница 13: ...ng to the previous menu or normal operation screen VIEW FIRE Viewing fire alarm messages VIEW FAULT Viewing fault messages VIEW DISABLE Viewing disabled messages VIEW PLANT Viewing messages of started fire suppression devices in the system SELF TEST Self testing the panel DISABLE Disabling a system device ENABLE Re enabling a disabled device CLOCK Modifying system time START Starting fire suppress...

Страница 14: ...rd is shown in Fig 3 2 Fig 3 2 Every loop card can drive 4 ZCPs All of them are connected together with a 10p ribbon cable through XS1 of the control board We can use the switch to set a code for each ZCP z No 1 1 6 8 at ON others at OFF z No 2 2 6 7 at ON others at OFF z No 3 3 5 8 at ON others at OFF z No 4 4 5 7 at ON others at OFF 3 2 2 Functions Fig 3 3 Each switch includes a red LED a yellow...

Страница 15: ...ess it again the silenced sounder strobes sound again and red LED goes out In silence mode when new alarm occurs all silenced sounder strobes activate again c Point device mode Single startable devices can also be defined on the ZCP Press the key corresponding device is initiated and red LED is lit Press the key again corresponding device stops red LED goes out 3 3 Configuration 3 3 1 Typical Conf...

Страница 16: ... switches on each loop card and communication card respectively representing tens digit and ones digit They are used to set the channel number of loop card and communication card The loop card is of dual channel The code switch sets the channel number of the first channel and automatically adding 1 for the second channel The numbers of communication card and loop card can be mixed randomly Example...

Страница 17: ...d 485 communication card and loop card A Motherboard Fig 3 6 shows the structure of the motherboard of the control panel installed on the bottom of the control part It connects with the DC DC convertor through terminals There are 10 channel slots for plugging main board loop card and communication cards The control panel is expandable to at most two motherboard boxes Signal Bus Channel Slot Commun...

Страница 18: ...eck AC Check 24V GND Switch Board 5V Display Board 5V Printer Fig 3 7 PSU24 6RM Intelligent PSU PSU24 6RM intelligent PSU is used to supply power to modules and corresponding controlled devices PSU24 6RM is shown in Fig 3 8 INTELLIGENT PSU Fig 3 8 A Indicators and switches MUTE Key Pressing MUTE can silence the PSU panel when fault occurs The sound will resume when new fault occurs TEST RESET Key ...

Страница 19: ...SE 10A ON ON GND 24V 10A GND 24V Fig 3 9 AC ON OFF AC ON applies AC power and AC OFF disconnects AC power BATTERY ON OFF BATTERY ON applies battery and BATTERY OFF disconnects battery BAT Battery input 24V GND EXTERNAL OUTPUT 24VDC main output 24V GND INTERNAL OUTPUT 24VDC multi wire power output AC socket 220V 230VAC power input including chassis earth 3 3 2 Optional Configuration 1 Fireman s Con...

Страница 20: ...equations can be downloaded from PC 3 4 Field Devices 3 4 1 A Series of Intelligent Fire Detectors GST 5000 can connect with a series of fire detectors such as I 9102 I 9103 and I 9105R The detectors installed in the protected area transmit monitoring message to the FACP through Class A loop Every detector has its own address with which the FACP can supervise the information of alarm fault and nor...

Страница 21: ...GST852RP Repeater Panel is designed with a microprocessor When one or more detectors alarm fire the repeater panel can display the location numbers and information of the detectors and send out audible and optical signals Through communication loops it can be connected with FACPs disposing and displaying the data transmitted from the FACPs When monitoring several floors or several zones with one F...

Страница 22: ...it to the FACP through the configuration software by PC according to engineering configuration 8 Commission and inspect field devices 4 1 Configuration Inspection 4 1 1 Check Engineering Configuration Check the configuration according to packing list The main items to be examined are Installation and Operation Manual keys to the FACP etc 4 1 2 Check Internal Configurations and Interconnection of t...

Страница 23: ...lative Humidity 95 non condensing Installation Space Width of maintenance of the FACP should be more than 1000mm 4 3 Start up Check After mounting GST5000 apply power to it as shown in Fig 4 2 Turn on the mains and battery switch in the cabinet and check if the FACP can self test The procedures are as follows 1 Check LCD digitron and indicators 2 Check self test on the stored running records disab...

Страница 24: ...eld Devices Loop interface board combines GST5000 FACP and field devices Terminals of loop interface board are shown in Fig 4 3 Fig 4 3 Description CLASS CHANGE XT3 Short it to make the sounders output FAULT OUTPUT XT8 Normally open contact is closed when fault signal Caution Do not connect power to your device until you have completed all input and output connections Fail to do so may result in i...

Страница 25: ...or in the ring detection loop the detector protected by loop isolator is not missing when there is short or open circuit In this case the FACP reports fault RS 485 XT11 XT12 To be connected with repeater panel and FACP earthX8 This terminal is for checking earth fault when there is short circuit F P E OUTPUT SOUNDER CIRCUIT OUTPUT FIRE ALARM OUTPUT can provide three output modes 24VDC active outpu...

Страница 26: ...er of sounder strobes Do not overload 4 4 2 Connection of F P E Output F P E output is shown in Fig 4 5 Fig 4 5 A 4 7kΩ resistor is connected at the F P E OUTPUT as factory default Please remove it and keep it well before connection After connecting the loop in correct polarity add the resistor to the end of the line NOTE F P Es are polarized Note polarization in connection The maximum current of ...

Страница 27: ...ire supervisory devices are polarized Note polarity in connection The maximum current of the circuit depends on the number of fire supervisory devices Do not overload 4 4 4 Connection of Class A Loop A Class A loop is shown in Fig 4 7 Fig 4 7 Note Every loop isolator can control maximum 32 detectors 4 4 5 Connection of Communication Loop LOOP OUT XT4 LOOP IN XT2 Addressable field devices Addressab...

Страница 28: ...d at different circuits and ground should be more than 20MΩ the resistance in the detection loop should be more than 1kΩ The resistance among fire alarm output sounder circuit output F P E output should be equal to end of line resistor 4 5 2 Registration of Devices Step One Set the FACP at commissioning state Up to 32 control panels B A Network XT11 Control Panel Control Panel Up to 64 repeater pa...

Страница 29: ...sion state The screen like Fig 4 11 will be shown on the LCD Fig 4 11 Step Two In commission state re start the FACP GST5000 FACP will automatically register devices Please check the number of devices registered programming and operation state comply to design requirement and remove any problem 4 6 Definition of Devices Please define devices and C E equation by configuration software GSTDef2 0 via...

Страница 30: ...n the LCD of the FACP following the steps below Step 1 Pressing SYSTEM to enter system setting menu as in Fig 4 12 Fig 4 12 Step 2 Choosing 5 Zone browse can browse the zone definition as shown in Fig 4 13 Fig 4 13 Notes Zone 0001 1floor Zone number and descriptions Ver V4 05f System setup 1 Modify password 2 Communicate setup 3 Working state setup 4 Fire display mode 5 Zone browse 6 C E browse 7 ...

Страница 31: ...ess BROWSE will enter the screen shown in Fig 4 14 All system configurations will be displayed Fig 4 14 Step 2 Check loop configuration Pressing any key in the screen shown in Fig 4 14 will enter the screen displaying loop configuration with the top line highlighted Pressing TAB the highlight will disappear and the FACP will check the loop Pressing and will move the highlight bar on different loop...

Страница 32: ... 4 16 Fig 4 16 Descriptions 016 Zone 001 016 Gas Det Message number user code zone number device number device type Browse Register info Loop 02 013 Points 016 Zone 001 016 Gas Det 1floor cookroom 017 Zone 002 017 Fix Temp 1 floor bathroom 032 Zone 003 032 Optical 1floor corridor 214 Zone 003 214 Fresh Air 1 floor toilet Browse Register info Loop00 000 Repeaters Loop01 000 points 000 Access Loop02...

Страница 33: ...ode zone number device number device type 1 floor toilet Zone description device description In device browsing state pressing and can turn pages In device selection state pressing and can change the selected device 4 6 3 Viewing C E The C E equations defined by the definition software can be browsed on the LCD of the FACP following the steps below Step 1 Pressing SYSTEM will enter system setting ...

Страница 34: ... the third piece of C E in the above figure No0003004 03 004 02 004 11 004 1300 This is a C E with foggy devices in which is an asterisk mark representing any number from 0 to 9 The meaning of this C E is If there is any photoelectric smoke detector or any rate of rise and fixed temperature heat detector alarms or any manual call point from Zone No 4 the sounder strobe of that zone will be started...

Страница 35: ...as real connection If most of devices are found missing check the power supply and loop isolators first then come to individual device Press SELF TEST key to check field device registration 3 Check whether registration of repeater panels is the same as the actual If there is any problem check the communication cable A and B and 24V power supply 4 Label the ZCP at the correct places 5 Carry out det...

Страница 36: ...te or the system displays improperly The normal display is shown in Fig 5 1 which means the system is in working state Then only POWER HEALTHY LED illuminates Fig 5 1 5 2 Information of Fire Alarm 5 2 1 Fire Alarm Screen FIRE LED is illuminates when there is fire alarm signal Speaker of the control panel sounds fire truck sound and corresponding fire LED on the ZCP is also lit There are two option...

Страница 37: ...ne 002 Time and zone of the third fire alarm FLOOR DINING ROOM Zone definition first 8 digits and device definition last 32 digits 004 16 34 zone 006 Time and zone of the forth fire alarm FLOOR LIVINGROOM Zone definition first 8 digits and device definition last 32 digits 005 16 34 zone 005 Time and zone of the fifth fire alarm 4 FLOOR BATHROOM Zone definition first 8 digits and device definition ...

Страница 38: ...ice address and type of the third fire alarm 1 FLOOR DINING ROOM Zone definition first 8 digits and device definition last 32 digits 004 16 34 zone 002 111 OPTICAL Time zone device address and type of the forth fire alarm 2 FLOOR LIVINGROOM Zone definition first 8 digits and device definition last 32 digits 005 16 34 zone 003 121 OPTICAL Time zone device address and type of the fifth fire alarm 3 ...

Страница 39: ...the factors that caused the false alarm Step Three Press RESET to make the FACP back to the normal state If the device still gives false alarm disable it and inform the installer or manufacturer for repair 5 3 Fault Information 5 3 1 Screen of Fault Information When there are fault signals different LEDs can be lit according to the type of fault If it is mains fault AC FAULT LED will be lit if it ...

Страница 40: ...ition first 8 digits and device definition last 32 digits 5 3 2 Disposal of Fault Information There are two kinds of fault One is system fault such as AC power and battery fault loop fault The other is field device fault like detector fault module fault etc If it is battery fault charge storage battery in time to avoid damage If the battery has powered the system overtime the FACP will power down ...

Страница 41: ...t zone number 001 of the device Step Two Press TAB the highlight position moves to next input zone Step Three Input device code number 016 Step Four Referring to Appendix 2 Device Type List input the device type 03 Press ENTER to save If the device has been disabled the screen will show Input Err if not the screen will add the device to the disablement information 2 Enabling the device Pressing EN...

Страница 42: ...W DISABLE you can browse disabled information of the device Pages are turned by pressing and Disabled information can only be displayed by device mode The window is shown in Fig 5 7 Fig 5 7 Description of disabled screen DISABLED total 100 Total number of the disabled information 001 16 34 zone 001 106OPTICAL Zone device address and type of disabled device 002 16 34 zone 001 103 OPTICAL Zone devic...

Страница 43: ... loop device and the screen is shown in Fig 5 8 Fig 5 8 The basic steps are as follows Step One Input the user code of the device to start Step Two Pressing TAB device type is highlighted Step Three Input the device type referring to Appendix 2 Device Type List Step Four Pressing ENTER the control panel gives start command After the device is started PLANT CONTROL LED and action indicator on the Z...

Страница 44: ... PLANT CONTROL LED and action indicator on the ZCP will be off 5 5 2 Operation of the Devices by ZCP According to definition of the ZCP press the key corresponding to the device and input the password by system indication you can start the device Corresponding command LED of the key is lit Press the key and input password again you can stop the device and the command LED turns off 5 5 3 Browsing S...

Страница 45: ...g and Silencing of the System First silencing the sound then pressing RESET can turn off all the control modules local outputs and all the detectors without changing the state of disabled devices The LCD displays information of RESET IN SYSTEM and all LEDs except for POWER HEALTHY AECURITY MODE and EXTINGUISHING SYSTEM PERMIT will be turned off The reset information will be written into running lo...

Страница 46: ...loop mode In any display mode the system will return to displaying message of the highest priority if there is no operations within 20s 15s 30s 5 8 Rules for Sound Indication When there is fire alarm or fault the speaker of the FACP will give sound indication The FACP gives fire truck sound when fire alarm occurs The FACP gives action sound when any device is activated Module action slow tick soun...

Страница 47: ...osition and returns to the first after the last position Wherever the cursor is Press ENTER key all the input data will be saved press ESC to exit present editing state without saving 6 1 3 Method of Browsing Information Entering browsing state press and to scroll for information Press ENTER the top piece of information becomes highlighted and the system enters information selection state Press TA...

Страница 48: ...time 6 digit user number event type and brief description of the event 6 digit user number If the event refers to an addressable device the first 3 digits show zone number the following 3 digits show the user code in this zone If the information is about loop or bus this number will be the loop or bus number Device type It shows the device type for device information or the operation type for syst...

Страница 49: ...3 History 12 06 10 45 000000 CRTFault Fault 12 06 10 40 000000 Reset 12 06 10 37 000000 AC Fault Back 12 06 10 28 000000 AC Fault Fault 12 06 10 20 010032 CableDet Fire 12 06 10 11 010056 HR Pump Start 12 06 10 05 020011 Sounder Act 12 06 10 01 030124 Heat Det Iso Press Enter to select an item History 12 06 10 45 000000 CRTFault Fault 12 06 10 40 000000 Reset 12 06 10 37 000000 AC RCL Back 12 06 1...

Страница 50: ...g SECURITY MODE needing password if the keypad is locked the system will get into security mode setting as shown in Fig 6 4 Fig 6 4 The system can be set as security enable and disable mode under this screen In enable mode the security alarm function is enabled to monitor the protected area by security detectors and SECURITY MODE LED illuminates 6 3 4 Extinguishing Mode Pressing EXTINGUISHING MODE...

Страница 51: ...ll be lit the gas release device can be started manually or automatically 6 3 5 Modification of System Time In monitoring state pressing CLOCK needing password if the keypad is locked the screen will display as in Fig 6 6 Input the time in the highlight area and then press TAB to move the highlight to next position Press ENTER to confirm Fig 6 6 Ver V4 05f System running Modify system time Enter t...

Страница 52: ...rrect password is input can a further operation be done User password for printer setting clock setting security mode setting start stop disable enable and the operation on ZCP and FACP reset Gas extinguishing control password for gas release enable control System password Entering SYSTEM menu for setting of system state and data Higher level password can substitute for lower level password System...

Страница 53: ...rrent operation Fig 6 9 Enter new password and press ENTER To prevent mistake the FACP requires entering the new password again Fig 6 10 If you typed the same password twice the screen shows a brief password display with a long beep sound and the system exits current operation showing the new password has been entered successfully If there are any mistakes the system will exit current operation wi...

Страница 54: ... setup you can enter communication setting menu Refer to Fig 6 11 Fig 6 11 Inputting 1 is to set CRT system Inputting 2 is to set remote telephone network system Inputting 3 is to set network system 6 4 3 Working State Setup In system setup menu in Fig 6 7 select 3 Working state setup Fig 6 12 Ver V4 05f Repeat new Enter new password Confirm password Ver V4 05f Communicate setup 1 Color CRT 2 Remo...

Страница 55: ...4 Fire Display Mode Select 4 Fire display mode under system setup menu Fig 6 7 the screen shows as in Fig 6 13 Fig 6 13 Inputting 1 fire information will be displayed by device Inputting 2 fire information will be displayed by zone 6 4 5 Zone Browse Refer to section 4 6 3 6 4 6 C E Equation Browse Refer to section 4 7 Ver V4 05f Display Mode 1 By Point 2 By Zone Ver V4 05f Working state setup 1 Mo...

Страница 56: ...represents viewing dynamic data It can read data of detectors in real time It monitors commissioning state of I 9105R Intelligent Beam Detector if the return value is between 680 750 it means the commission is successful 3 represents viewing static data 4 represents immediate start of gas extinguishing devices If the command of Turn on gas release 24V gas extinguishing devices will be started at o...

Страница 57: ... the registering information will not be saved When the FACP is restarted the missing or damaged devices will not be reported These functions are only for commissioning 7 1 Getting into Commission Mode Enter system setup menu Fig 6 7 select 3 Working state setup Fig 7 1 Fig 7 1 Press and select 2 Commissioning State confirm to enter commissioning state the word Installer will appear on top of the ...

Страница 58: ... be disabled with the same method as detectors The device type is 59 The user number is the loop number The disabled loop will stop bus output and stop the communication with the main board The Enable operation can cancel the disablement to the loop card 7 5 Detector Searching Under Commission Mode the detectors can be forced into alarming state by keypad operation It will be easy to find the loca...

Страница 59: ...fault still exists replace the batteries 4 The loop cards can t be registered correctly 1 The loop cards are not inserted correctly 2 The addresses of loop cards are wrongly set 1 Check and insert correctly 2 Check addresses of the loop cards 5 The display panel can t be registered The communication cable is not connected correctly Check the cables for the display panel 6 Not printing 1 Print mode...

Страница 60: ...larly 1 The print paper should be replaced as required prior to running out Fig 8 1 1 Remove the printer front cover as shown in Fig 8 1 2 Remove the whole printer from the panel Please nip the movable tongues on the two sides with fingers according to Fig 8 2 remove the whole printer from the panel gently Note Before removing the printer make sure to turn off the power to the printer Remove ...

Страница 61: ...Generic Part The Intelligent Solution Page 56 Fig 8 2 3 Remove the scroll spindle Fig 8 3 Fig 8 3 4 Put the new scroll on the spindle And press the scroll spindle into the groove of the printer as in Fig 8 4 Make sure the scroll spindle is installed firmly Press Press Pull Push Up ...

Страница 62: ...ing to Fig 8 5 Fig 8 5 6 Turn on the power of the printer Press SEL key to turn off the SEL light Then press LF to move the head Feed the paper through by hand the paper will enter slowly until it appears in front of the head Feed through a suitable length of paper Press LF or SEL again or turn off the power Replace the front cover of the printer Feed the Push down ...

Страница 63: ...e control panel gently 8 If according to engineering configuration the back of the control panel display part is not covered by other structures it is easier to take the paper from the back Replacement of paper can be carried out according to steps 3 4 5 and 6 2 The background light of the LCD has a life range When any problem is found in its brightness please inform the supplier ...

Страница 64: ...nual Generic Part The Intelligent Solution Page 59 Chapter 9 Calculation of Battery Capacity The equation for calculating battery capacity is as follows Battery Capacity Ah 0 84 T 0 03 N 3 5 In which N is the number of detectors and T is the time of operation in standby state ...

Страница 65: ...2 XS1 XT1 16 24V XS5 GND Z1 Z2 24V XT4 GND GND XT3 24V GND XT4 24V GND XT3 24V C12 C11 C13 C12 C13 C14 C14 17 C2 C2 C1 C1 XT2 XT1 XS1 XT4 GND 24V XT3 GND 24V or to router board to RS485 To RS232 RJ45 connector to Loudspeaker 13 XS1 Number Name Number Name Number Name Number Name 1 Motherboard 6 Loop interface board 11 Printer 16 Main board of fireman s control panel 2 Loop card 7 100W power 12 LCD...

Страница 66: ...OUT REPEATER B A RS 485 NETWORK A B GND C1 XS1 XS1 15 C12 C13 C13 C12 C11 C11 C2 C1 C1 C1 C2 XT1 XT2 C2 C2 C1 C1 XT2 C2 C1 C1 C2 XT1 24V GND 24V GND 14 XT3 XT4 24V 24V GND GND XT4 XT3 XS1 XS2 Z1 GND 24V Z2 24V GND XS5 13 XS1 LOOP IN SOUNDER CIRCUIT POUTPUT FIRE ALARM OUTPUT F P E OUTPUT RJ45 connector 220V Ground Battery Battery Number Name Number Name Number Name Number Name 1 Motherboard 6 DC DC...

Страница 67: ...HR Pump 16 Hydrant pump SPKR Pmp 17 Sprinkler pump PS SW 18 Stabilized pressure pump Extract 19 Smoke exhauster Presuriz 20 Blower FreshAir 21 Fresh air Damper 22 Fire damper SM Vent 23 Smoke vent Air Inlet 24 Air inlet SolValve 25 Solenoid valve SM CURT 26 Roller shutter door middle point RSD Clse 27 Shutter screen door close point FireDoor 28 Fire door PS DIFF 29 Pressure switch Flow SW 30 Water...

Страница 68: ...uge pump Undefine 52 Undefined Stop Mod 53 Device stop Silence 54 Mute key SounderA 55 Fire alarm sounder SounderF 56 Fault sounder Loop SW 57 Loop switch CRT Fault 58 CRT Fault Loop 59 Loop PSU Bat 60 Battery PSU AC 61 AC power Lock 62 Multi wire lock PART 63 Part of devices ZoneDir 64 Zone direction F P E 65 Fire protection equipment All evac 66 Evacuation Ground f 67 Ground fault ...

Страница 69: ...RT To start a device password required BROWSE Viewing registration information password required CLOCK Modifying the system time password required ENABLE To de disable the disabled device password required STOP To stop a started device password required LOG Browsing history record SECURITY MODE To set security mode password required EXTINGUISHING MODE To set gas release mode password required PRIN...

Страница 70: ...com cn GST UK Global System Technology PLC Lion Court Staunton Harold Hall Melbourne Road Ashby de la Zouch Leicestershire England LE65 1RT Tel 44 1283 225 478 Fax 44 1283 220 690 Email info gst uk com www gst uk com GST Dubai Global System Technology PLC PO Box 17998 Unit ZA04 JEBEL ALI Free Zone Dubai UAE Tel 971 0 4 8833050 Fax 971 0 4 8833053 Email info gst uk com www gst uk com ...

Отзывы: