![GST GST5000 Скачать руководство пользователя страница 15](http://html1.mh-extra.com/html/gst/gst5000/gst5000_installation-and-operation-manual_2275591015.webp)
GST5000 Intelligent Fire Alarm Control Panel
Installation and Operation Manual (Generic Part)
The Intelligent Solution
Page 10
a) Zone direction mode [ZoneDir]
When fire occurs in a zone, corresponding red LED is lit and the sounder strobe is
automatically initiated; when fault occurs, corresponding yellow LED flashes; when
disabling all devices in the zone, corresponding yellow LED is constantly lit.
When pressing the key of the zone, the sounder strobe is initiated; press again, it is
stopped.
b) Silence mode [Silence]
Press this key, all connected sounder strobes are silenced and red LED lit; press it
again, the silenced sounder strobes sound again, and red LED goes out. In silence
mode, when new alarm occurs, all silenced sounder strobes activate again.
c) Point device mode
Single startable devices can also be defined on the ZCP. Press the key, corresponding
device is initiated and red LED is lit. Press the key again, corresponding device stops,
red LED goes out.
3.3 Configuration
3.3.1 Typical Configuration
(1) Wall-mounted GST5000W FACP
A typical FACP system consists of a control cabinet, a loop interface board, a P.S.U
system, display and operation area and a ZCP.
①
Control cabinet
Cabinet is the core part of the FACP, mainly consisting of 3 parts: motherboard, main
board, and loop card. RS232 and RS485 communication cards can be inserted like in
Fig. 3-4.
A: Motherboard Illustration
Fig. 3-4