Fig. 4-17
Meaning of the above C&E:
The part before the "
=
” refers to the condition, and the part after “
=
” is the result.
“
×
” means “and” and “+” means or.
NO.0001 refers to the first piece of C&E.
Composition of the condition part of the C&E.
001 001 03
Device type
Device address
Zone number of the device
Composition of the result part of the C&E.
001 004 13 00
Delay time
Device type
Device address
Zone number of the device
In the third piece of C&E in the above figure,
No0003004***03+004***02+004***11=004***1300
This is a C&E with foggy devices, in which “*” is an asterisk mark representing any
number from 0 to 9. The meaning of this C&E is: If there is any photoelectric smoke
detector or any rate of rise and fixed temperature heat detector alarms or any manual
call point from Zone No. 4, the sounder strobe of that zone will be started.
Step 3: Viewing spaces for the C&Es.
Ver V4.05f
C&E Formula Browser
1. General C&E
2. Extinguishing C&E
No000100100103×000100203×00100303
+
00100103×0100303
+
00100103×00100203×00100303
=
00100413 00
No000200200103×000200203×00200303
+
00200103×0100303
+
00200103×00200203×00200303
=
00200513 00
No0003004***03+004***02+004***11=004***1300