GST5000 Intelligent Fire Alarm Control Panel
Installation and Operation Manual (Generic Part)
The Intelligent Solution
Page 7
Chapter 3 Structure and Configuration
3.1 Display and Operation Area
The display and operation area is shown in Fig. 3-1, which consists of LCD display,
indicators, clock display, keypad and printer.
0
8
5
4
7
*
9
6
×
=
2
1
3
+
CLOCK
GST5000 Intelligent Fire Alarm Control Panel
Fig. 3-1
3.1.1 Indicators
FIRE: Red. This LED lit means the FACP has checked fire alarm state of
connected detectors. Detailed messages are shown on the LCD. When fire
alarm is cleared, press
RESET
key to turn it off.
COMMON FAULT: Yellow. Lit when any fault occurs.
DISABLED: Yellow. Lit when connected devices, F.P.E. output or SOUNDER
output are disabled.
MUTE: Yellow. When the FACP sounds alarm, pressing
MUTE
key, this LED
illuminates, and the speaker stops alarming. If
MUTE
key is pressed again or
there are new alarms, it goes out and the FACP sounds again.
POWER HEALTHY: Green. It illuminates when mains or standby battery of
the system works normally.
SYSTEM FAULT: Yellow. Lit when the program fails or the system cannot
operate normally.
AC FAULT: Yellow. Lit when mains power is cut off or defected, and goes out
when it resumes.
BATTERY FAULT: Yellow. Lit when standby power system is in fault and goes
out when it’s cleared.
F.P.E. FLT/DISABLE: Yellow. Lit when F.P.E. output is in fault or is disabled.