![GST GST5000 Скачать руководство пользователя страница 17](http://html1.mh-extra.com/html/gst/gst5000/gst5000_installation-and-operation-manual_2275591017.webp)
GST5000 Intelligent Fire Alarm Control Panel
Installation and Operation Manual (Generic Part)
The Intelligent Solution
Page 12
keypad (such as browsing, setting, and printing).
⑤
Zone indication and manual intervention panel (ZCP)
Indicating fire, and fault/disablement of corresponding devices, and starting or stopping
them.
(2) Typical configurations of GST5000 rack type and console type:
Comparing with wall mounted type, the rack and console types can have more loop
cards connected to the control cabinet and an intelligent PSU is used.
①
Control Cabinet
Main control unit is the core part of the control panel, including motherboard, main board,
232 communication card, 485 communication card and loop card.
A: Motherboard
Fig. 3-6 shows the structure of the motherboard of the control panel installed on the
bottom of the control part. It connects with the DC-DC convertor through terminals.
There are 10 channel slots for plugging main board, loop card and communication cards.
The control panel is expandable to at most two motherboard boxes.
Signal Bus
Channel Slot
Communication Bus in Parallel
Communication Bus in Parallel
Fig. 3-6
Communication bus in parallel: Used for system extension
Channel Slot: Used to plug main board, loop card and communication card on.
XP3: Connecting with DC-DC convertor
ZAn, ZBn
(
n=1
~
20
)
: 1
~
10 channel signal bus terminals
Note: When DC-DC convertor is switched off, loop 24V is not cut off. If you want
to plug in or pull out the circuit boards in the main unit, please disconnect main
and standby power.
Содержание GST5000