GST5000 Intelligent Fire Alarm Control Panel
Installation and Operation Manual (Generic Part)
The Intelligent Solution
Page 18
Fig. 4-1
4.2.2 Installation condition and method of rack type and console-typed FACP.
Rack (L
×
W
×
H): 580mm
×
520mm
×
1540mm (or 1715mm)
Console(L
×
W
×
H, single unit): 555mm
×
933mm(with table)
×
1350mm
Console(L
×
W
×
H, double unit):1045mm
×
933mm (with table)
×
1350mm
Ambient Temperature: 0
℃~
+40
℃
Relative Humidity
≤
95%, non-condensing
Installation Space: Width of maintenance of the FACP should be more than 1000mm.
4.3 Start-up Check
After mounting GST5000, apply power to it as shown in Fig. 4-2. Turn on the mains and
battery switch in the cabinet and check if the FACP can self-test. The procedures are
as follows.
(
1
)
Check LCD, digitron and indicators.
(
2
)
Check self-test on the stored running records, disablement information and
C&E equations.
(
3
)
Observe whether the indicators, and digitron on the FACP and ZCP can all be lit
and whether the speaker gives three continuous alarm sounds and “beep” tone.