GST5000 Intelligent Fire Alarm Control Panel
Installation and Operation Manual (Generic Part)
The Intelligent Solution
Page 34
32 digits)
Press Enter to Select an Item //Press
ENTER
to view a fire alarm message.
5.2.2 Disposal of Fire Alarm Signal
When fire alarm occurs, first find out the location according to the information shown on
the FACP to verify whether the fire really happened.
If it’s a real fire, please take corresponding measures.
Step One: Evacuate the people in field.
Step Two: Call the fire department.
Step Three: Initiate extinguishers.
If it is a false alarm, please take the following measures.
Step One: Press
SILENCE
to stop the sound.
Step Two: Remove the factors that caused the false alarm.
Step Three: Press
RESET
to make the FACP back to the normal state. If the device
still gives false alarm, disable it and inform the installer or manufacturer for repair.
5.3 Fault Information
5.3.1 Screen of Fault Information
When there are fault signals, different LEDs can be lit according to the type of fault. If it
is mains fault,
AC FAULT
LED will be lit; if it is standby power fault,
BATTERY FAULT
LED will be lit; if it is system fault,
SYSTEM FAULT
LED will be lit; if it is field device fault,
relative LED on the ZCP is lit. Speaker of the FACP gives alarm sound (ambulance
sound).
Fault information can only be displayed by device, the screen is shown in Fig. 5-4.
Fig. 5-4
Ver V4.05f
!FAULT! Total 100
001 16:34 zone 002
-
03 OPTICAL
1 FLOOR COOKROOM
002 16:34 zone 002-101 OPTICAL
1 FLOOR DINING ROOM
003 16:34 zone 002-111 OPTICAL