![GST GST5000 Скачать руководство пользователя страница 40](http://html1.mh-extra.com/html/gst/gst5000/gst5000_installation-and-operation-manual_2275591040.webp)
GST5000 Intelligent Fire Alarm Control Panel
Installation and Operation Manual (Generic Part)
The Intelligent Solution
Page 35
Description of the fault screen:
Each fault message occupies two lines. You can view different fault message by
pressing
△
=
and
=
▽
.
!FAULT! total 100//Total fault events.
001 16:34 zone 002
-
03 OPTICAL// Time, zone, device address and type of the
fault event.
1 FLOOR COOKROOM// Zone definition (first 8 digits) and device definition (last
32 digits)
002 16:34 zone 002-101 OPTICAL// Time, zone
,
device address and type of the
fault event.
1 FLOOR DINING ROOM// Zone definition (first 8 digits) and device definition (last
32 digits)
003 16:34 zone 002-111 OPTICAL// Time, zone device address and type of the
fault event.
2 FLOOR LIVINGROOM // Zone definition (first 8 digits) and device definition (last
32 digits)
5.3.2 Disposal of Fault Information
There are two kinds of fault. One is system fault, such as AC power and battery fault,
loop fault. The other is field device fault, like detector fault, module fault etc.
If it is battery fault, charge storage battery in time to avoid damage. If the battery
has powered the system overtime, the FACP will power down for protection.
If it is system fault, check and repair in time. If power-down is needed, make
detailed notes.
If it is field device fault, it should be repaired immediately. You can disable it if the
fault cannot be cleared for some reason. Then enable it when the device fault is
repaired.
5.4 Disable and Enable
5.4.1 Use of Disable/Enable
When some problems happen to the field device, it may be necessary to disable the
device for maintenance, and then re-enable it after repairing or replacing.
5.4.2 Disable/Enable Devices
1) Disabling a device