53
11.4 Baldor Smart motor settings
Section
Parameter
Grundfos setting
Value
Level 2 blocks
Output limts
Min. output frequency
12 Hz
Output limts
Max. output
60 Hz
Output limts
PK current limit
Max. of drive
Output limts
PWM frequency
6 kHz
Miscellaneous
Restart aut/man
Auto
Motor data
Motor voltage
230 V
Motor data
Motor rated amps
SFA on nameplate
Level 1 blocks
Preset speed
Preset speed #1
60 Hz
Accel
Accel #1
CR 3 - CR 10
1.5 sec.
CR 15 - CR 90
2.0 sec.
Decel rate
Decel #1
CR 3 - CR 10
3.0 sec.
CR 15 - CR 90
4.0 sec.
Output
Opto output #1
Ready
Input
Operating mode
#1 2 wire / 7 spd
Input
ANA CMD select
Pot. / 0-10 V
V/Hz and Boost
V/Hz profile
67% sqr. law