10.7.14 Forced pump changeover (4.2.4)
Fig. 40
Forced pump changeover
Description
This function ensures that the pumps run for the same number of
operating hours. In certain applications the requirement remains
constant for long periods and does not require all pumps to run.
In such situations, pump changeover does not take place
naturally, and forced pump changeover may thus be required.
Once every 24 hours the controller checks if any pump running
has a larger number of operating hours than pumps that are
stopped. If this is the case, the pump is stopped and replaced by
a pump with a lower number of operating hours.
Setting range
The function can be activated/deactivated. The hour of the day at
which the changeover is to take place can be set.
Setting via control panel
1. Mark the
Settings
menu with
.
2. Mark
Pump cascade control
with
or
and press
.
3. Mark
Forced pump changeover
with
or
and press
.
4. Mark
Activated
with
or
and press
. The check
mark in the right box shows that the function is active.
5. Mark
Time for changeover
with
and press
.
6. Set the time with
or
and save with
.
Factory setting
The function is activated. The time is set to 03:00.
10.7.15 Test run (4.2.5)
Fig. 41
Test run
Description
This function is primarily used in situations where the forced
pump changeover is deactivated, and/or if the Hydro MPC is set
to operating mode
Stop
, for instance in a period when the system
is not needed. In such situations, its important to test the pumps
regularly. The function ensures that
•
pumps do not seize up during a long standstill due to deposits
from the pumped liquid.
•
the pumped liquid does not decay in the pump.
•
trapped air is removed from the pump.
Each pump is connected to a counter.
The pump starts automatically one by one and runs for 5
seconds.
Note:
Pumps in
Manual
operating mode are not included in the
test run. If there is an alarm, the test run will not be carried out.
Setting range
•
Not used
•
Once every 24 hours.
•
Once every 48 hours.
•
Once a week.
Setting via control panel
1. Mark the
Settings
menu with
.
2. Mark
Pump cascade control
with
or
and press
.
3. Mark
Test run
with
or
and press
.
4. Mark the desired function with
or
.
5. Activate the function with
.
Factory setting
Test runs are set to once a week.
10.7.16 Secondary functions (4.3)
Fig. 42
Secondary functions
Description
Functions that are secondary in relation to the normal operation
of the Hydro MPC booster set can be set in this display.
Secondary functions are functions that offer additional
functionality. The display makes it possible to open specific
displays regarding:
•
•
Overview of digital inputs (4.3.7)
•
Overview of analog inputs (4.3.8)
•
Overview of digital outputs (4.3.9)
•
Min., max. and user-defined duty (4.3.14)
•
•
.
T
M
03
23
65
40
05
TM
03
23
64
40
05
TM
03
23
32
40
05
www.motralec.com / [email protected] / 01.39.97.65.10
Содержание BoosterpaQ Hydro MPC
Страница 12: ...12 INSTALLATION AND STARTUP NOTES www motralec com service commercial motralec com 01 39 97 65 10 ...
Страница 54: ...54 Variable frequency drive setting notes www motralec com service commercial motralec com 01 39 97 65 10 ...
Страница 58: ...58 www motralec com service commercial motralec com 01 39 97 65 10 ...