Setting range
The following functions can be selected:
•
Dry-running protection (4.4.1)
•
•
•
Setting via control panel
1. Mark the
Settings
menu with
.
2. Mark
Monitoring functions
with
or
and press
.
3. Select the function with
or
and press
.
Factory setting
No function has been selected.
10.7.33 Dry-running protection (4.4.1)
Fig. 60
Dry-running protection
Description
Dry-running protection is one of the most important monitoring
functions, as bearings and shaft seal may be damaged if the
pumps run dry. Grundfos thus "requires" dry-running protection in
connection with Hydro MPC booster sets.
The function is based on monitoring of the inlet pressure or the
level in a possible tank or pit on the suction side.
Level switches, pressure switches or analog sensors signalling
water shortage at a set level can be used.
There are three different methods for detection of water shortage:
•
Pressure switch on suction manifold or float switch/electrode
relay in the supply tank.
•
Measurement of inlet pressure in the suction manifold by
means of an analog pressure transmitter.
•
Measurement of level in the supply tank by means of an ana-
log level transmitter.
Setting via control panel
1. Mark the
Settings
menu with
.
2. Mark
Monitoring functions
with
or
and press
.
3. Mark
Dry-running protection
with
or
and press
.
4. Select the method with
or
and press
Factory setting
If a pressure switch or pressure transmitter is fitted on the suction
manifold, the relevant function has been selected and set.
10.7.34 Dry-running protection with pressure/level switch
(4.4.1.1)
Fig. 61
Dry-running protection with pressure/level switch
Description
Dry-running protection can take place by means of a pressure
switch on the suction manifold or a level switch in a possible tank
on the suction side.
When the contact is
open
, the CU 351 will register water
shortage after a time delay of approx. 5 sec. It is possible to set
whether the indication is to be just a warning or an alarm stopping
the pumps.
In the display it is possible to set whether restart and reset of the
alarm is to be automatic or manual.
Setting range
•
Selection of digital input for the function.
•
Reaction in case of water shortage: Warning or alarm + stop.
•
Restart: Manual or automatic.
Setting via control panel
1. Mark the
Settings
menu with
.
2. Mark
Monitoring functions
with
or
and press
.
3. Mark
Dry-running protection
with
or
and press
.
4. Mark
Pressure/level switch
with
or
and press
.
5. Mark
Go to setting of digital input
and press
. Now the
display
Overview of digital inputs (4.3.7)
input to dry-running protection. Return with
.
6. Mark
Warning
or
Alarm + stop
with
or
and save with
.
7. Mark
Manual
or
Auto
with
or
and save with
.
Factory setting
If the booster set is equipped with a pressure switch for dry-
running protection, it is set to alarm + stop in case of water
shortage.
Restart: Automatic.
TM
03
23
20
40
05
TM
03
2
329
4
005
www.motralec.com / [email protected] / 01.39.97.65.10